3

MI.50.J1.02 - VLT is a registered Danfoss trademark

VLT

®

 Series 5000  Wobble function

701

Center frequency  (CENTER FREQ)

Value:

0.0 - 120.0 Hz

 25.0Hz

Function:

The center frequency of the wobble sequence is

specified in this parameter.

Description of choice:

The center frequency is specified in Hertz. The output

frequency can not exceed the setting of parameter

200.

704

Jump time  (JUMP TIME)

Value:

0 - 50 ms

 0 ms

Function:

This parameter determines the slope of the jump

ramp at the maximum and minimum wobble

frequency.

This parameter can only be changed in stop-mode.

Description of choice:

The time is specified in milliseconds.

702

Delta frequency  (DELTA FREQ)

Value:

0.0 - 20.0 Hz

 5.0Hz

Function:

The delta frequency is determining the magnitude of

the wobble frequency. The delta frequency is

superimposed on the center frequency. Parameter

702 is selecting both the positive and negative delta

frequency. The setting of parameter 702 must thus

not be higher than the setting of parameter 701.

The initial ramp up time from standstill until the

wobble sequence is running is determined by

parameter 207.

Description of choice:

The frequency is specified in Hertz.

703

Jump frequency  (JUMP FREQ)

Value:

0.0 - 25.0 Hz

 0.0Hz

Function:

The jump frequency is used to compensate for the

inertia in the traverse system.

If a jump in the output frequency is required in the top

and in the bottom of the wobble sequence, the

frequency jump is set in this parameter.

If the traverse system has a very high inertia a high

jump frequency may create a torque limit warning or

trip (warning/alarm 12) or an over voltage warning or

trip (warning/alarm 7).

This parameter can only be changed in stop-mode.

Description of choice:

The frequency is specified in Hertz.

705

Wobble time  (WOBBLE TIME)

Value:

0.0 - 1000.0 s

 10.0 s

Function:

This parameter determines the wobble sequence

period.

This parameter can only be changed in stop-mode.

Wobble time = t

up 

+ t

down

Description of choice:

The time is entered in seconds.

706

Wobble ratio  (WOBB RATIO)

Value:

0.1 - 10

 1

Function:

The ratio between the up time versus the down time

of the wobble sequence is specified in this parameter.

Wobble ratio = t

up

/t

down,

This parameter can only be changed in stop-mode.

Description of choice:

If the ratio 

0.1

 is selected:

 t

down

 is 10 times  greater than t

up

.

If the ratio

10

 is selected:

 t

up

 is 10 times greater than t

down

.