VLT® 5000 Crane
Appendix
■
Control Word in Crane Profile
Control word in Crane profile (parameter
512 = crane profile)
The control word is used for sending commands from
a master, eg. a PC, to a slave (frequency converter).
Bit
Bit = 0
Bit = 1
00
Load contact 1
inverse
No function
01
Load contact 2
inverse
No function
02
No function
Positioning
03
Coasting inverse
No function
04
Quick stop inverse
No function
05
Ramp stop
Start lowering
06
Ramp stop
Start hoisting
07
No function
Reset
08
No function
09
Gear low
Gear high
10
Data not valid
Data valid
11
No function
Relay 01 activated
12
No function
Relay 04 activated
13
No function
14
No function
15
No function
NB!:
In Crane profile bit 04 Q stop is the only choice
for logic OR, logic AND and logic BUS.
Bit 00, Load contact 1 inverse/No function
Bit 00 = "1" means no speed reduction.
Bit 01, Load contact 2 inverse/No function
Bit 01 = "0" leads to further descreased speed (
parameter 702) if bit 00 = "0". Otherwise it leads to
a Trip. Bit 01 = "1" means no speed reduction.
Bit 00
Bit 01
Load high
0
0
Load low
0
1
Trip
1
0
No
function
1
1
Bit 02, No function/Positioning
Makes the motor turn with reduced speed
according to parameters 106, Motor Nominal
Speed, and 205, Max. reference.
Bit 02 = "0" means no reduced speed. Bit 02
= "1" means reduced speed.
Bit 03, Coasting inverse/No function
Please refer to
Control word in FC profile
.
Bit 04, Quick stop inverse/No function
Please refer to
Control word in FC profile
.
Bit 05, No function/Start lowering
Makes the motor turn to lower the load opposite of the
direction set in parameter 707, Hoist direction.
Bit 05 = "0" leads to a stop if bit 06 = "0". Bit 05 = "1"
leads to start if bit 06 = "0". Otherwise it leads to a stop.
Bit 05
Bit 06
Stop
0
0
Stop
1
1
Hoisting
0
1
Lowering
1
0
Bit 06, No function/Start hoisting
Makes the motor turn to hoist the load according to the
direction set in parameter 707, Hoist direction.
Bit 06 = "0" leads to a stop if bit 05 = "0". Bit 06 = "1"
leads to start if bit 05 = "0". Otherwise it leads to a stop.
Bit 07, No function/Reset
Please refer to
Control word in FC profile
.
Bit 09, Gear low/Gear high
Enables gear low or high. Bit = "0" is low
gear. Bit = "1" is high gear.
Bits 10-12
Please refer to
Control word in FC profile
.
MG.50.N4.02 - VLT is a registered Danfoss trademark