Using this Quick Setup, you can carry out quick
and EMC-correct installation of the frequency
converter (Fig. 1) in five steps. (Fig. 1: *= Start/
stop). The Operating Instructions, which are also
enclosed, give other examples of installation and
describe all functions in detail.

Read the safety instructions on this page before
installing the unit.

Mechanical installation

Mechanical installation

Mechanical installation

Mechanical installation

Mechanical installation
VLT 2800 frequency converters allow side-by-
side installation on a wall. Because of the need for
cooling, there must be 10 cm free air passage
above and below the frequency converter.

Drill holes in accordance with the measurements
given in fig. 2. Please note the difference in unit
voltages.

Retighten all four screws.

Fit the decoupling plate to the power cables and
the earth screw (terminal 95).

VLT

®

 2800  Quick Setup

Fig. 2

Electrical installation, power

Electrical installation, power

Electrical installation, power

Electrical installation, power

Electrical installation, power
Please note that the power terminals can be
removed.

Connect mains to the mains terminals of the
frequency converter, i.e. L1, L2, L3 and the earth
connection to terminal 95 (Fig. 3).

Fit a screened/armoured cable from the motor to
the motor terminals of the frequency converter,
i.e. U, V, W (Fig. 3). The screen ends in a screen
connector.

Fig. 1

Fig. 4

Electrical installation, control cables

Electrical installation, control cables

Electrical installation, control cables

Electrical installation, control cables

Electrical installation, control cables
Remove the front cover underneath the control
panel. Place a jumper between terminals 12 and
27. (Fig. 4).

In parameter 002

 Local/remote control,

 the

frequency converter mode can be selected as

Remote operation

 [0], i.e. via the control

terminals, or

 Local

 [1], i.e. via the control unit.

Set the control location to 

Set the control location to 

Set the control location to 

Set the control location to 

Set the control location to 

Local 

Local 

Local 

Local 

Local 

[1]

[1]

[1]

[1]

[1]

.....

Local/remote operation = 

Local 

[1] Par.  002

Set the motor speed by adjusting the 

Set the motor speed by adjusting the 

Set the motor speed by adjusting the 

Set the motor speed by adjusting the 

Set the motor speed by adjusting the 

Local

Local

Local

Local

Local

reference

reference

reference

reference

reference

Local reference

Parameter 003

Motor start

Motor start

Motor start

Motor start

Motor start
Press [Start] to start the motor. Set the motor
speed by adjusting parameter 003 

Local

reference

.

Check whether the direction of rotation of the
motor shaft is clockwise. If not, exchange any
two phases on the motor cable.
Press [STOP/RESET] to stop the motor.
Press [QUICK MENU] to return to display
mode.
(QUICK MENU] + [+] keys must be pressed
simultaneously to give access to all
parameters.

Safety regulations

Safety regulations

Safety regulations

Safety regulations

Safety regulations
The voltage of the frequency converter can be
fatal whenever it is connected to mains. Incorrect
installation of the motor or the frequency
converter may lead to damage to the equipment,
serious personal injury or death.

Consequently, the provisions of this Quick Setup,
as well as national and local rules and safety
regulations, must be complied with.

Touching the electrical parts may be fatal, even
after the equipment has been disconnected from
mains: wait at least 4 min.

1.

The mains supply to the frequency

converter must be disconnected if repair work is
to be carried out.
2.

The [STOP/RESET] key on the control

panel of the frequency converter does not
disconnect the mains supply and is thus not to
be used as a safety switch.
3.

Correct protective earthing of the unit must

be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4.

The earth leakage current is higher than 3.5

mA.
5.

Protection against motor overload is not

included in the factory setting. If this function is
required, set parameter 128 

Motor thermal

protection

 to data value 

ETR Trip

 or 

ETR

Warning

.

6.

Check that the mains supply has been

disconnected before removing the motor and
mains plugs.

Warning against unintended start

Warning against unintended start

Warning against unintended start

Warning against unintended start

Warning against unintended start
1.

The motor can be brought to a stop by

means of digital commands, bus commands,
references or local stop, while the frequency
converter is connected to mains. If personal
safety considerations make it necessary to
ensure that no unintended start occurs, these
stops are not sufficient.
2.

While parameters are being programmed,

the motor may start. Consequently, the stop key
[STOP/RESET] must always be activated,
following which data can be modified.
3.

A motor that has been stopped may start if

faults occur in the electronics of the frequency
converter, or if a temporary overload, a fault in
the supply mains or a fault in the motor
connection ceases.

VLT 2803-2815 200-240 V
VLT 2805-2815 380-480 V

*

Programming

Programming

Programming

Programming

Programming
Carry out programming on the control panel.

Press the [QUICK MENU] key to enter the Quick
menu.
In this menu, parameters can be selected by
means of the [+] and [-] keys. The parameter
values can be changed by pressing [CHANGE
DATA].
Changes are programmed using the [+] and [-]
keys.
Finish the change of a parameter setting by
pressing [CHANGE DATA].
A change of parameter values is saved automa-
tically after a mains failure.
If the display shows three dots at the right, the
parameter value has more than three digits. In
order to see the value, activate [CHANGE DATA].

Press [QUICK MENU]:

Set the motor parameters that are on the

Set the motor parameters that are on the

Set the motor parameters that are on the

Set the motor parameters that are on the

Set the motor parameters that are on the
nameplate of the motor:

nameplate of the motor:

nameplate of the motor:

nameplate of the motor:

nameplate of the motor:

Motor power [kW]

parameter 102

Motor voltage [V]

parameter 103

Motor frequency [Hz]

parameter 104

Motor current [A]

parameter 105

Rated motor speed

parameter 106

Activate AMT

Activate AMT

Activate AMT

Activate AMT

Activate AMT:::::

Automatic motor tuning

parameter 107

Set reference range

Set reference range

Set reference range

Set reference range

Set reference range

Min. reference, Ref

MIN

parameter 204

Max. reference, Ref

MAX

parameter 205

Set ramp times

Set ramp times

Set ramp times

Set ramp times

Set ramp times

Ramp-up time [s]

Parameter 207

Ramp-down time [s]

Parameter 208