
VLT® 2800 Series
Installation
■
Data readout:
Display mode
In normal operation, one item of operating data can
be displayed continuously at the operator
’
s own
choice. By means of the [+/-] keys the following
options can be selected in Display mode:
-
Output frequency[Hz]
-
Output current [A]
-
Output voltage [V]
-
Intermediate circuit voltage [V]
-
Output power [kW]
-
Scaled output frequency f
out
x p008
Menu mode
In order to enter the Menu mode [QUICK MENU] +
[+] must be activated at the same time.
In Menu mode, most of the variable frequency drive
parameters can be changed. Scroll through the
parameters using the [+/-] keys. While scrolling in the
Menu mode proceeds, the parameter number will flash.
The display shows that the setting in parameter
102
Motor power P
M,N
is 0.75. In order to change
the value of 0.75, [CHANGE DATA] must first
be activated; the parameter value can then be
changed using the [+/-] keys.
If for a given parameter the display shows three
dots at the right, it means that the parameter
value has more than three digits. In order to see
the value, activate [CHANGE DATA].
The display shows that in parameter 128
Motor thermal
protection
the selection made is
Thermistor trip
[2].
Quick menu
Using the [QUICK MENU] key, it is possible to access
the 12 most important parameters of the variable
frequency drive. After programming, the variable
frequency drive is in most cases ready for operation.
When the [QUICK MENU] key is activated in Display
mode, the Quick menu starts. Scroll through the quick
menu using the [+/-] keys and change the data values
by first pressing [CHANGE DATA] and then changing
the parameter value with the [+/-] keys.
The Quick menu parameters are:
•
Par. 102
Motor power P
M,N
•
Par. 103
Motor voltage U
M,N
•
Par. 104
Motor frequency f
M,N
•
Par. 105
Motor current I
M,N
•
Par. 106
Rated motor speed n
M,N
•
Par. 107
Automatic motor adaption
•
Par. 204
Minimum reference Ref
MIN
•
Par. 205
Maximum reference Ref
MAX
•
Par. 207
Ramp-up time
•
Par. 208
Ramp-down time
•
Par. 002
Local/remote operation
•
Par. 003
Local reference
Parameter 102 - 106 can be read out from
the motor
’
s nameplate.
Programming the adjustable frequency drive
NOTE
The motor must be stopped to change
parameter data.
Program the drive in accordance with the
following procedure:
1. Press the [QUICK MENU] key to enter
the Quick menu.
MG.28.A8.22 - VLT is a registered Danfoss trademark
25