VLT® 2800 Series
■
Control unit
On the front of the variable frequency drive
there is a control panel.
The control panel is divided into five functional groups:
1. Status LED
2. Keys for changing parameters and shifting
display function.
3. LEDs.
4. Keys for local operation.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating
data continuously during normal operation. As a
supplement to the display, there are three LEDs
for indication of electrical connection (ON), warning
(WARNING) and alarm (ALARM). Most of the
variable frequency drive
’
s parameter Setups can be
changed immediately via the control panel, unless
this function has been programmed as
Locked
[1]
via parameter 018
Lock for data changes
.
■
Control keys
[QUICK MENU]
allows access to the parameters
used for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA]
is used for changing a setting.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
[+] / [-]
are used for selecting parameters and
for changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
The
[QUICK MENU] + [+]
keys must be
pressed at the same time to give access to all
parameters. See
Menu mode.
[STOP/RESET]
is used for stopping the
connected motor or for resetting the variable
frequency drive after a trip.
Can be selected as
Active
[1] or
Not active
[0] via
parameter 014
Local stop/reset
. In Display mode, the
display will flash if the stop function is activated.
NOTE
If the [STOP/RESET] key is set at
Not active
[0] in parameter 014
Local stop/reset,
and
there is no stop command via the digital
inputs or serial communication, the motor can
only be stopped by disconnecting the electrical
voltage to the variable frequency drive.
[START]
is used for starting the variable frequency
drive. It is always active, but the [START] key
cannot override a stop command.
■
Manual initialization
To manually initialize the adjustable frequency drive to
factory default settings, first disconnect AC line voltage.
Hold the [QUICK MENU] and [+] and [CHANGE DATA]
keys down while simultaneously reconnecting the AC
line voltage. Release the keys. The drive has now
been programmed for factory settings.