6

VMBQE102

Specified output for heat transfer fluid in relation to the airflow 

The chart applies to:
Air temperature In +20 °C
Relative humidity 50 %
Temp. Brine In 0 °C
Ethylene alcohol 29 %

Introduction . control equipment
The extraction fan (FF) is phase controlled. The fan capacity can be changed between 20-99%. Adjustment 

is described in the instructions on page 7. 
The Circulation pump CP is continuously controlled. If the temperature falls below the set temperature at 

GT1 the circulation pump CP stops for a set time (factory setting = 5 minutes) and until the temperature 

has risen to the set value. The LED at the bottom right of the display lights when the circulation pump CP is 

in operation.

Settings
To access the service menus, keep the arrow button depressed for 3 seconds.
Use the arrow buttons to scroll between the menus. Quick calculations can be made if the arrow button is 

held in. If a button is not pressed for 10 minutes the display returns to normal view, room temperature at 

GT4.
GT2, GT3 and GT4 are only for temperature readings and have no controlling function.

N (normal view)

5.0 Temperature display at GT4

FL (filter alarm)

Filter alarm display (reset using -/+ for 3 

secs)

Service menus

Menu

Factory set .

Min/Max

Explanation

1

0 °C

-3 / 3

Temperature display GT1 (calibrating)

2

0 °C

-3 / 3

Temperature display GT2 (calibrating)

3

0 °C

-3 / 3

Temperature display GT3 (calibrating)

4

0 °C

-3 / 3

Temperature display GT4 (calibrating)

5

0 °C

-10 / 10

Setting temp. GT1 stop circ.pump

Energy transfer

Summary of Contents for Vent

Page 1: ...anning and installation instructions 3 2 1 Ventilation 3 2 2 Piping installation 3 2 3 Condensation line 4 2 4 Electrical Installation 4 3 Adjustment 5 3 1 Ventilation 5 3 2 Piping installation 5 4 Op...

Page 2: ...m cleaner to clean the filter We recommend replacing the filter once a year Heat recovery unit The hot extracted air passes a water coil and transfers its heat to the water that comes from the ground...

Page 3: ...oup B according to high current regulations The duct system must fulfil leak class B The exhaust air duct and extracted air duct must be installed with silencers before being connected to the unit The...

Page 4: ...e unit is started and stopped using the switch located under the control panel In position 0 the unit s electrical components should be treated as conductors Electrical connection circulation pump Cir...

Page 5: ...or hoods must not be connected to the system The fan capacity is described in the diagram on page 4 and is set according to the instructions on page 6 3 2 Piping installation The water flow through t...

Page 6: ...lights when the circulation pump CP is in operation Settings To access the service menus keep the arrow button depressed for 3 seconds Use the arrow buttons to scroll between the menus Quick calculat...

Page 7: ...lation pump 0 Stationary 1 Operational High current 1 FF controlled phase 2 FF phase capacitor fan 3 FF capacitor fan 120 W 230VAC 10 4 CP 5 CP 6 7 Phase 230VAC 10 8 Neutral 4A Control diagram Data In...

Page 8: ...vent imbalance resulting in unnecessary bearing damage 4 The fan bearings are maintenance free and must only be replaced if necessary 5 Do not use a high pressure washer or strong cleaning agents whe...

Page 9: ...t is supplied with a plug for an earthed wall socket 1 phase 230 V Dimension details and connections 1 Bleeding 2 Water IN Cu 15mm 3 Water OUT Cu 15mm 4 Air IN connection dim 160mm 5 Air OUT connectio...

Page 10: ...ICAL INSTALLATION Date Company Name Tel No If these instructions are not followed during installation operation and maintenance Danfoss AS s liability according to the applicable warranty is not bindi...

Page 11: ...11 VMBQE102...

Page 12: ...VMBQE102...

Reviews: