7.4.5 RS485 Commissioning and Cabling
7.4.5.1 General Cabling Instructions for RS485
Use only shielded cables with twisted-pair signal wires.
For example, the following cables are recommended:
•
Lapp Kabel UNITRONICR BUS LD FD P A, part number 2170813 or 2170814
•
Belden 9841
The plug type to be used is 2.5 mm
2
(AWG13).
The theoretical maximum cable length depends on baud rate. See the following table for suggested maximum cable lengths.
Table 20: The RS485 Cable Lengths
Baud rate (kbit/s)
Length of line A (m)
Length of line B (m)
9.6
1200
1200
19.2
1200
1200
93.75
1200
1200
187.5
1000
600
500
400
200
1500
200
-
3000–12000
100
-
Control Unit
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
78 | Danfoss A/S © 2019.05