Appendix A: Power Line Accessories Installation
1. Figure A-69 shows a schematic of the main input circuit and connections to the line
reactor. Use this schematic as a guide for choosing the location of the line reactor.
2. Feed the AC line cable through the opening in the side of the main supply panel.
3. Attach the AC line wires to the line reactor terminals as shown in Figure A-70.
4. Attach the ground cable to the mounting block on the panel wall. Ensure there is good
electrical/mechanical contact between the ground cable and the panel wall.
5. Secure the AC line cable to the main supply panel using approved methods (i.e., cable
gland)
1. Feed the AC line cable through the opening in the side of the main supply panel.
2. Attach the AC line wires to the line reactor output terminals as shown in .
3. If a harmonic filter is being installed, attach its AC line wires to the line reactor output
terminals.
4. Attach the ground wire to the mounting block on the panel wall. Ensure there is good
electrical/mechanical contact between the ground wire and the panel wall.
5. Secure the AC line cable to the main supply panel using approved methods (i.e. cable
gland).
6. See Section 4.6 “Power Wiring” for instructions on completing the AC input connection
to the compressor.
These instructions apply to the installation of the line reactor kit in a main supply panel. See
the
Spare Parts Selection Guide
for product specifications.
A.1.1 AC Line Cable
Connection (From
External Disconnect)
A.1.2 AC Line Cable
Connection (to
Compressor Terminal)
A.1 Line Reactor
Installation Instructions
NOTE
The customer is responsible for supplying the mounting hardware for the line reactor.
Summary of Contents for Turbocor TT Series
Page 2: ...Page 2 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 8: ...Page 8 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Page 18 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...Page 32 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...Page 36 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 44: ...Page 44 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...Page 50 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 52: ...Page 52 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 54: ...Page 54 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...Page 56 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 58: ...Page 58 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 70: ...Page 70 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 74: ...Page 74 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 82: ...Page 82 of 108 M AP 001 EN Rev N Physical Data Figure 16 9 Suction Port All Models...
Page 88: ...Page 88 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 90: ...Page 90 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...Page 92 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK...