RS485
Terminate the RS485 communication bus at both ends.
To terminate the RS485 bus:
•
Connect Bias L to RX/TX B
•
Connect Bias H to RX/TX A
The RS485 address of the inverter is unique, and defined at the factory.
Illustration 5.8: RS485 Communication Detail - Cat 5 T-568A
Pinout RS485
1. GND
2. GND
3. RX/TX A (-)
4. BIAS L
5. BIAS H
6. RX/TX B (+)
7. Not connected
8. Not connected
Bold = Compulsory, Cat5 cable
contains all 8 wires
For Ethernet: 10Base-TX and
100Base-TX auto cross over
Table 5.8: RJ45 Pinout Detail for RS485
Ethernet
Ethernet connection is available for TLX CN Pro and TLX CN Pro+ variants only.
Pinout
Ethernet
Colour Standard
Cat 5
T-568A
Cat 5
T-568B
1. RX+
Green/white
Orange/white
2. RX
Green
Orange
3. TX+
Orange/white
Green/white
4.
Blue
Blue
5.
Blue/white
Blue/white
6. TX-
Orange
Green
7.
Brown/white
Brown/white
8.
Brown
Brown
Table 5.9: RJ45 Pinout Detail for Ethernet