TP7001
14
GB
Option 90 - Defi ne Remote Sensor Type
(Remote sensor 1 - Backplate connection b)
This allows type of remote sensor input type to be
defi ned. Press
+
until Option 90 is displayed, use
V
or
Λ
to select required setting.
0 = No Sensor (Factory setting)
1 = Remote room or Duct sensor, internal sensor
disabled
2 = Remote limit (fl oor) sensor, defi ne setpoint in
option 93
3 = Digital input for window, card reader, or teleswitch,
defi ne functionality in option 94
4 = Outdoor temperature sensor (information only -
no control via sensor reading)
Option 91 - Defi ne Remote Sensor Type
(Remote sensor 2 - Backplate connection C)
This allows type of remote sensor input type to be
defi ned. Press
+
until Option 91 is displayed, use
V
or
Λ
to select required setting.
0 = No Sensor (Factory setting)
1 = Remote room or Duct sensor, internal sensor
disabled
2 = Remote limit (fl oor) sensor, defi ne setpoint in
option 93
3 = Digital input for window, card reader, or teleswitch,
defi ne functionality in option 94
4 = Outdoor temperature sensor (information only -
no control via sensor reading)