Danfoss Heating
15
GB
Option 92 - Defi ne Remote Sensor Type
(Remote sensor 3 - Backplate connection d)
This allows type of remote sensor input type to be
defi ned. Press
+
until Option 92 is displayed, use
V
or
Λ
to select required setting.
0 = No Sensor (Factory setting)
1 = Remote room or Duct sensor, internal sensor
disabled
2 = Remote limit (fl oor) sensor, defi ne setpoint in
option 93
3 = Digital input for window, card reader, or teleswitch,
defi ne functionality in option 94
4 = Outdoor temperature sensor (information only -
no control via sensor reading)
Note: Only one of each type of sensor may be fi tted - the choices
within options 90-92 will automatically be limited once remote
sensor types are chosen.
Option 93 - Set Limit Sensor Set-Point
(One of options 90-92 set to 2)
This allows the thermostat limit sensor to be set,
typical application is fl oor heating. Press
+
until Option
93 is displayed, use
V
or
Λ
to select required setting. If
the temperature sensed by the limit sensor exceeds
the limit setting the output will be turned off until the
temperature has dropped by 2°C. “F10” will fl ash in the
display while the output is disabled.
This option is only possible if one remote sensor
option is set to Remote Limit (Floor) Sensor (Setting
2)
Any value between 20.0ºC and 50.0ºC in 0.5.0ºC steps
Factory setting is 27ºC
The temperature set for the limit point sensor will be determined by
the type of fl oor. The recommended limits are:
Tiles on chipboard and wooden fl oors 27°C
Carpet or vinyl on chipboard 35°C
Tiles on concrete fl oor 40°C
Concrete, screed, etc 45°C