4.2 Start-up

Start-up, Heating with mixing loop

Start-up:

1: Pump speed

Set the pump to highest speed before start-up.

2: Start pump

Start the pump and heat through the system.

3: Open shut-off valves

The shut-off valves should then be opened and the unit observed
as it enters service. Visual checking should confirm temperatures,
pressures, acceptable thermal expansion and absence of leakage.
If the system operates in accordance with design, it can be put
to regular use.

4: Vent system

Switch off the pump and vent the installation after the radiators
have been warmed up.

5: Adjust pump speed

Set the pump to the lowest speed consistent with comfort and
electricity consumption.
Normally the change-over switch is set in the mid position (default).
However for systems with under floor heating or single pipe loop
systems, it may be necessary to turn the change-over switch
upwards.
Higher pump speeds are only used if the heating requirement
increases.

Re-thighten connections

After water has been added to the system and the system has been
put into operation, re-tighten

ALL

connections.

Pump

The pump must be switched off during system fill.

Under floor heating:

Pump stop function

If the substation is used in connection with under floor heating, the
circulation pump must be connected to the pump stop function in
the under floor heating controller. The pump must be stopped if
all under floor heating circuits are closed.

Warranty

If this is not possible, then flow must be continued through the
by-pass. Failing this, the pump will be at risk of seizure and any
remaining warranty will be withdrawn.

Summer operation:

Switch off pump

In summer the circulation pump must be switched off and the
shut-off valve to HE supply closed.

Running pump bi-weekly

It is recommended to start up the circulation pump (for 2 minutes)
once a month during summer; the shut-off valve of the HE supply
must be shut.

Electronic controller

Most electronic controllers will start up the pump automatically
(please note manufacturer´s instructions).

Danfoss Heating

VI.CW.W2.02 / LUK41200

DEN-GT

7

Summary of Contents for Termix VMTD Compact 20

Page 1: ...up 7 4 3 Electrical connections 8 5 0 Design 9 5 1 Design 9 5 2 Schematic diagram 10 6 0 Controls 12 6 1 Heating circuit 12 6 2 DHW temperature control 14 6 3 Other 15 6 4 Maintenance 17 7 0 Troublesh...

Page 2: ...Installation Guide Termix VMTD Compact 20 2 DEN GT VI CW W2 02 LUK41200 Danfoss Heating...

Page 3: ...troller sets the optimum operation conditions for radiator thermostats in order to enable individual temperature control in each room The mixing loop creates a suitable temperature level for the heati...

Page 4: ...rcumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves on the substation inform th...

Page 5: ...nnections 1 District heating DH supply 2 District heating DH return 3 Heating HE supply 4 Heating HE return 5 Domestic hot water DHW 6 Domestic cold water DCW 7 Hot water circulation HWC Connection si...

Page 6: ...and rinse Prior to installation all substation pipes and connections should be cleaned and rinsed Thightening Due to vibration during transport all substation connections must be checked and tightene...

Page 7: ...f the heating requirement increases Re thighten connections After water has been added to the system and the system has been put into operation re tighten ALL connections Pump The pump must be switche...

Page 8: ...ted for repairs Outdoor temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direct sunlight They should not be placed close to doors windows or ventilation outlets The outd...

Page 9: ...t look different than the substation shown Design description B Heat exchanger DHW 11 Domestic hot water pump F Electronic controller 27 Actuator HE 7 Thermostatic controller DHW 31 Differential press...

Page 10: ...fferent than the schematic diagram shown Schematic description B Heat exchanger DHW 11 Domestic hot water pump 24 Delivered loose with unit F Electronic controller heating 16 Outdoor sensor 27 Actuato...

Page 11: ...sor 27 Actuator 2 Single check valve 18 Thermometer 29 2 way motorized valve 7 Thermostatic valve 19 Surface sensor 31 Differential pressure controller DHW Domestic Hot Water DCW Domestic Cold Water H...

Page 12: ...e HE flow temperature in the heating circuit is controlled by the HE temperature controller Thermostatic control The temperature of the HE flow line is adjusted as follows To increase temperature turn...

Page 13: ...n be used as safety function by power failure 6 1 4 Electronic control Substations with electronic control must be set in accordance with manufacturer s instructions Where the room temperature is cont...

Page 14: ...ed operation The variable speed modulating modes allow the pump to match its performance to the system requirements helping to reduce noise when thermostatic valves are closing down Energy labelling c...

Page 15: ...2 Electric 2 way motorized valve Actuators with or without safety function are available for 3 point controls Spring return actuators can be used to provide safety shut off in the event of power fail...

Page 16: ...ating conditions and the manufacturer s instructions 6 3 3 Domestic hot water pump Important It is necessary to mount a domestic hot water circulation pump on the water heater to avoid regulation prob...

Page 17: ...Checking of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should be checked by...

Page 18: ...ump Defective or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed instructions for el...

Page 19: ...required Air pockets in the system Vent the installation thoroughly Limiting of the return temperature adjusted too low Adjust according to instructions Defective radiator valves Check replace Uneven...

Page 20: ...ols as well as return sensors Pump pressure too high Adjust pump to a lower level Air in system Vent the system Defective or incorrectly set radiator valve s Single pipe loop systems require special o...

Page 21: ...Installation Guide Termix VMTD Compact 20 Danfoss Heating VI CW W2 02 LUK41200 DEN GT 21...

Page 22: ...Installation Guide Termix VMTD Compact 20 22 DEN GT VI CW W2 02 LUK41200 Danfoss Heating...

Page 23: ...ent of machines EMC Direct ive 2004 108 EEC EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromagnetic compatibility Generic standard Emission...

Page 24: ...Installation Guide Termix VMTD Compact 20 Produced by Danfoss A S 01 2012...

Reviews: