6.1.3 Strainer

Strainers should be cleaned regularly by authorized personnel. The
frequency of cleaning would depend on operating conditions and
the manufacturer’s instructions.

6.1.4 GTU Pressure Equalizer

The GTU Pressure Equalizer absorbs the expansion on the
secondary side of the Termix water heaters and can be used as a
substitute to the safety valve.
Furthermore the pressure equalizer absorbs a possible increase in
pressure, so a discharge outlet is omitted.
The GTU Pressure Equalizer may not be applied in systems with hot
water circulation.

6.2 Maintenance

The substation requires little monitoring, apart from routine
checks. It is recommended to read the energy meter at regular
intervals, and to write down the meter readings.

Regular inspections of the substation according to this Instruction
are recommended, which should include:

Strainers

Cleaning of strainers.

Meters

Checking of all operating parameters such as meter readings.

Temperatures

Checking of all temperatures, such as DH supply temperature and
DHW temperature.

Connections

Checking all connections for leakages.

Safety valves

The operation of the safety valves should be checked by turning
the valve head in the indicated direction.

Venting

Checking that the system is thoroughly vented.

Inspections should be carried out minimum every two years.

Spare parts can be ordered from Danfoss. Please ensure that any
enquiry includes the substation serial number.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by

qualified and authorized personnel only.

10

DEN-GT

VI.CW.J3.02 / LUK38000

Danfoss Heating

Summary of Contents for Termix One-B

Page 1: ...ral 3 4 0 Mounting 4 4 1 Mounting 4 5 0 Design 6 5 1 Design 6 5 2 Schematic diagram 7 6 0 Controls 9 6 1 DHW temperature control 9 6 2 Maintenance 10 7 0 Troubleshooting 11 7 1 Troubleshooting in gene...

Page 2: ...ly thereby creating a very good operation economy Domestic hot water DHW The domestic hot water is prepared in the heat exchanger and the temperature is regulated with a thermostatic control valve The...

Page 3: ...rous circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves on the substation in...

Page 4: ...1 Domestic cold water DCW 2 Domestic hot water DHW 3 District heating DH supply 4 District heating DH return Connection sizes DH G int thread DCW DHW G int thread Dimensions mm Type 1 2 without cover...

Page 5: ...rinse Prior to installation all substation pipes and connections should be cleaned and rinsed Thightening Due to vibration during transport all substation connections must be checked and tightened bef...

Page 6: ...B 5 0 Design 5 1 Design Your substation might look different than the substation shown Design description B Heat exchanger DHW O Termix sensor accelerator 7 Thermostatic controller DHW 6 DEN GT VI CW...

Page 7: ...Second diagram Termix One Q with safety valve Schematic description B Heat exchanger DHW 7 Thermostatic valve 2 Single check valve 21 To be ordered separately 4 Safety valve 62 GTU Pressure equalizer...

Page 8: ...parameters Technical parameters Nominal pressure PN 16 Max DH supply temperature 120 C Min DCW static pressure 0 5 bar Brazing material HEX Copper Heat exchangers test pressure 30 bar Sound level 55 d...

Page 9: ...of up to 90 C Thermostatic control DHW temperature is adjusted as follows To increase temperature turn the handle on the thermostatic controller to select a higher number To decrease temperature turn...

Page 10: ...gular intervals and to write down the meter readings Regular inspections of the substation according to this Instruction are recommended which should include Strainers Cleaning of strainers Meters Che...

Page 11: ...efective or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed instructions for electro...

Page 12: ...7 3 Disposal Disposal This product should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regulations 12 DEN GT VI C...

Page 13: ...Installation Guide Termix One B Danfoss Heating VI CW J3 02 LUK38000 DEN GT 13...

Page 14: ...Installation Guide Termix One B 14 DEN GT VI CW J3 02 LUK38000 Danfoss Heating...

Page 15: ...gory 0 without electrical equipment covered by this declaration are in conformity with the following directives standards and other normative documents provided that they are used according to our ins...

Page 16: ...Installation Guide Termix One B Produced by Danfoss A S 05 2013...

Reviews: