Operating Guide
Termix BTD RO MIX
6.1.4 AVTB controller (30–100 °)
The temperature setting is as follows:
1 = 35 °C
2 = 55 °C
3 = 75 °C
4 = 95 °C
5 = 100 °C
The values are intended as a guide.
Thermostatic control
The temperature of the HE flow line is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
6.1.5 Electronic control
Substations with electronic control must be set in accordance with
manufacturer´s instructions.
Where the room temperature is controlled by radiator thermostats,
it is recommended that thermostats be set for minimum
temperature in each room.
6.1.6 Outdoor temperature sensor (ESMT)
Outdoor sensors should be mounted so as to avoid exposure to
direct sunlight. They should not be placed close to doors, windows
or ventilation outlets.