Safety Notes

Prior to assembly and commissioning to 

avoid injury of persons and damages of 

the devices, it is absolutely necessary to 

carefully read and observe these instructions.
Necessary assembly, start-up, and maintenance 

work must be performed only by qualified, 

trained and authorized personnel. 
Prior to assembly and maintenance work on the 

controller, the system must be:

- depressurized, 

-  cooled down,

-  emptied and 

- cleaned.

Please comply with the instructions of the 

system manufacturer or system operator.

Disposal instruction

This product should be dismantled and 
its components sorted, if possible, in 

various groups before recycling or disposal.
Always follow the local disposal regulations.

Definition of Application 

Safety temperature monitor (actuator) STM is, 

in combination with Danfoss valves (STM/VG(F), 

VGS) and Danfoss controller combinations (STM/

AVT/VG(F), VGS), used for temperature control 

and temperature monitoring of drinking water, 

water and water glycol mixtures for heating and 

district heating systems. 

The controllers STM/VG(F), VGS and STM/AVT/

VG(F), VGS are:

-  Type-tested acc. to EN 14597
and protect against exceeding temperatures:

-  District heating systems acc. to DIN 4747

-  Heating systems acc. to EN 12828 (DIN 4751) 

and EN 12953-6 (DIN 4752) 

-  Water heating systems for drinking and 

industrial waters acc. to DIN 4753

The technical parameters on the product labels 

determine the use.

Application examples 

Safety temperature monitor (actuator) STM can 

be combined with:

•  VG(F) and VGS valves.

•  Combination pieces K2, K3, AVT actuators 

and valves mentioned above

Assembly

Admissible Installation Positions 

Safety temperature monitor (actuator)with 

valves 

In combination with VG(F) valves:

- Can be installed in any position 

.

In combination with VGS valves:

•  Medium temperatures up to 160 °C:

-  Can be installed in any position 

.

•  Medium temperatures > 160 °C:

-  Can be installed horizontal and in 

horizontal pipelines with the actuator 
oriented downwards 

.

Temperature sensor

•  The capillary tube may not be twisted or 

buckled. The minimum bending radius is 

50 mm.

•  The place of installation must be chosen in 

a way that the temperature of the medium 

is directly taken without any delay. Avoid 

overheating of temperature sensor.

•  The temperature sensor must be immersed 

into the medium in its full length 

.

•  The temperature sensor may be installed in 

any position 

.

Installation Location and Installation 

Scheme 

STM/valve 

,

STM/AVT/valve flow mounting 

Valve Installation 

1.  Clean pipeline system prior to assembly.

2.  Install a strainer in front of the controller 

Max. mesh width:

-  DN 15-25: 0,5 mm

-  DN 32-50: 0,8 mm

3.  Install temperature indicators in the system 

part to be controlled.

4. 

Install valve 

•  The flow direction indicated on the product 

label 

 or on the valve 

 must be observed.

•  The valve with mounted weld-on tailpieces 

may only be spot welded to the pipeline 

.

 

The weld-on tailpieces may be welded only 
without the valve and seals! 

⑤⑥

 

If these instructions are not observed, high 

welding temperatures may destroy the seals.

• Flanges 

 in the pipeline must be in parallel 

position and sealing surfaces must be clean 

and without any damage.

 

Tighten screws in flanges crosswise in 3 

steps up to the maximum torque (50 Nm).

5. 

Caution:

 

Mechanical loads of the valve body by 
the pipelines are not permitted.

Mounting of safety temperature 

monitor (actuator) 

Before mounting the actuator, carry out Filling 
the system, First start-up and Leak and pressure 
tests,

 

❽❾

.

Place temperature actuator at the valve 

 or 

combination piece 

 and tighten union nut 

with wrench SW 50. Torque 35 Nm.

Insulation 

Do not insulate the safety temperature 
monitor (actuator) and the valve as well.

Start-up 

 

Note

 

Valves 

 VG(F) and VGS are normally opened 

(NO) valves.

Filling the system and Leak and pressure test 
should be done without mounted 

temperature actuator 

 – valve has to be open.

Filling the system, first start-up 

1.  Slowly open shut-off devices 

 in the flow 

pipeline.

2.  Slowly open shut-off devices 

 in the return 

pipeline.

Leak and Pressure Tests 

Pressure must be gradually increased at the +/- 

side of the valve.

Do not test with closed valve! 

Non-compliance may cause damages at the 
actuator or the valve.

A pressure test of the entire system must be 

carried out in accordance with anufacturer’s 

instructions.

The maximum test pressure for the valves is:

1,5 × PN

PN - see product label

Putting out of operation

1.  Slowly close shut-off devices 

 in the flow 

pipeline.

2.  Slowly close shut-off devices 

 in the return 

pipeline. 

Settings 

Temperature Setting

The temperature setting range is indicated on 
product label 

.

Pre-conditions

The system must be opened and the flow of the 

medium guaranteed.

Procedure:

•  Set desired set point by turning the setting 

adjuster 

 with the delivered Allan key 

SW 5 

.

You may only adjust within the marked 
range, see 

.

 

Turning to the left (couter-clockwise) 

increases the set point. 

 

Turning to the right (clockwise) reduces the 

set point.

•  Observe temperature indicator.

•  Wait for about 3 to 5 min. until the 

temperature indicator shows the final value.

•  If the device is used as a temperature 

monitor, the setting adjuster 

 must be 

sealed by a sealing wire 

.

Temperature setting - AVT

(relevant only at STM/AVT/VG(F), VGS 

controllers)

See instructions for temperature actuator AVT.

Safety function 

If there is a leakage in the area of the 
temperature sensor 

, the capillary tube 

or the thermostat 

, the valve is closed by a 

pressure spring in the safety thermostat. In this 

case safety temperature monitor (actuator) 

must be replaced.

Dimensions, Weights 

1)

  Conical ext. thread acc. to EN 10226-1

2)

  Flanges PN 25, acc. to EN 1092-2

Summary of Contents for STM/VG

Page 1: ...EDERLANDS Temperatuurbeveiliging regelelement STM www danfoss com Pagina 8 POLSKI Stra nik temperatury bezpiecze stwa si ownik STM www danfoss com Strona 9 STM www danfoss com 10 SLOVEN INA Pogon varn...

Page 2: ...2 Danfoss 2017 08 VI GC X2 8K STM STM VG STM VGS DN 15 50 STM VG DN 15 25 STM AVT VGS DN 15 25 STM VGS DN 15 50 STM VGF DN 15 50 STM AVT VG DN 15 50 STM AVT VGF STM VGS...

Page 3: ...Danfoss 2017 08 3 VI GC X2 8K STM DN L mm 15 69 20 74 25 79 32 104 40 114 50 134...

Page 4: ...4 Danfoss 2017 08 VI GC X2 8K STM VG VGF...

Page 5: ...0 1 1 2 70 G 2A 47 195 204 110 18 4 50 2 82 G 2 A 60 252 234 125 18 4 DN L L1 H H1 H2 H3 H4 mm 15 65 130 224 274 34 47 301 20 70 150 224 274 34 52 301 25 75 160 224 274 37 57 301 32 100 180 266 266 62...

Page 6: ...to be controlled 4 Install valve The flow direction indicated on the product label or on the valve must be observed The valve with mounted weld on tailpieces may only be spot welded to the pipeline T...

Page 7: ...geschraubten Anschwei enden nur an die Rohrleitung anheften Das Einschwei en der Anschwei enden ist nur ohne Ventil und Dichtungen zul ssig Bei Nichtbeachtung zerst ren die hohen Schwei temperaturen d...

Page 8: ...udt rekening met de stromingsrichting zoals aangegeven op het typeplaatje of op de regelafsluiter zelf Een regelafsluiter met voorgemonteerde laskoppelingen enkel met een puntlas vastzetten De laskopp...

Page 9: ...towo przyspawany do ruroci gu Ko c wki mog by przyspawane tylko bez zaworu i uszczelnienia Niezastosowanie si do tego zalecenia mo e spowodowa uszkodzenie uszczelnie wskutek wysokiej temperatury przy...

Page 10: ...VG F VGS STM AVT VG F VGS 3 STM VG F VGS STM AVT VG F VGS EN 14597 DIN 4747 EN 12828 DIN 4751 EN 12953 6 DIN 4752 DIN 4753 VG F VGS 2 3 AVT VG F VGS 160 C 160 C 50 STM STM AVT 1 2 15 25 0 5 32 50 0 8...

Page 11: ...Danfoss 2017 08 11 VI GC X2 8K STM SW 5 3 5 AVT STM AVT VG F VGS AVT 1 EN 10226 1 2 P 25 EN 1092 2...

Page 12: ...12 Danfoss 2017 08 VI GC X2 8K STM...

Page 13: ...Danfoss 2017 08 13 VI GC X2 8K STM...

Page 14: ...14 Danfoss 2017 08 VI GC X2 8K STM...

Page 15: ...Danfoss 2017 08 15 VI GC X2 8K STM...

Page 16: ...s reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady a...

Reviews: