background image

14 | © Danfoss | Energy Meters | 2017.03 VUIGB702

Installation & User Guide 

SonoSelect and SonoSafe

4.2 

Display explanation

Working symbol

Supply/return mounted installation

Accumulated  energy

Alarm

Accumulated  flow

Service/maintenance

Total hours

Battery full or low

Instant power

Wired communication

Instant flow

Wireless communication

Supply temperature

Pulse

Return temperature

Decimal emphasizer

Temperature difference

Units field

4.3 Alarms

E01

System error 

E10

Transducer error

E02

PCB error 

E11

Outside measured range

E03

Battery empty (less than 1 month)

E12

Negative flow

E04

Battery low voltage

E13

Tamper alarm

E05

Battery low (less than 12 months)

E14

High flow > qss

E06

Supply Temperature Error 

E15

Battery consumption too high

E07

Return Temperature Error 

E16

Display overflow (energy/volume)

E08

Absolute/Difference temperature outside 
accumulated range

E32

Communication module error

E09

Low transducer signal

Summary of Contents for SonoSelect 10

Page 1: ...1 03 2017 Danfoss VUIGB602 www heating danfoss com Installation User Guide SonoSelect and SonoSafe energy meters...

Page 2: ...2 Danfoss Energy Meters 2017 03 VUIGB702 Installation User Guide SonoSelect and SonoSafe Note To ensure latest version of declaration please visit danfoss com...

Page 3: ...ow sensor installation 5 2 4 Mounting orientation calculator 5 2 5 Mounting of O ring and temperature sensor 6 2 6 Communication Expansion modules 7 2 7 Installation of module cable 10 2 8 Battery 11...

Page 4: ...ed the meter will set alarm E13 in display Don t open unless for adding communica tion module replacing battery or installing cables Reset requires Bluetooth dongle 014U1963 and SonoApp service tool S...

Page 5: ...stallation Heat meters have red temp sensor in supply pipe and all cooling meters have blue temp sensor in supply pipe 2 3 Flow sensor installation Pipe position No limitations but avoid positions whe...

Page 6: ...w sensor installation 1 Mount O ring on pin 2 Insert pin with O ring 3 Position O ring 4 Remove pin 5 Moist and insert sensor probe Tighten at torque 12 2 Nm To ensure accuracy and a tight seal the se...

Page 7: ...he display Wired M Bus is galvanically isolated from C and pulse inputs The two pulse inputs can be programmed independently of each other see specification for pulse input module M Bus primary Lithiu...

Page 8: ...evel input threshold 0 5 V Pull up resistor 100 k Pulse length 100 ms Maximum frequency 5 Hz Pulse inputs According to EN1434 2 section 7 1 5 Classification of pulse input devices Class IB Battery lif...

Page 9: ...orange 24 Meter bus blue or orange 25 Pulse input Pulse input 1 Brown 50 Pulse input 1 White 51 Pulse input 2 Brown 52 Pulse input 2 White 53 Cable specification Pulse input cables 10 m To ensure IP...

Page 10: ...to enclosure 4 Insert module follow ing guide on PCBA cover Insert cable through hole connect cable and fix to screw termi nals matching color and terminal numbers Fix cable s to cable relief Outer ja...

Page 11: ...n en closure 3 Disconnect battery connector and remove battery 4 Short circuit battery connectors on PCB using a small flat head screwdriver 5 Connect new battery to PCB 6 Fit battery in enclosure 7 C...

Page 12: ...s 4 For SonoSelect Run installation check using Bluetooth dongle 014U1963 and SonoApp service tool 3 2 Supply return configuration Only available for SonoSelect Use Bluetooth dongle 014U1963 and SonoA...

Page 13: ...e SonoSelect and SonoSafe 4 Function overview 4 1 Menu structure Hours Alarm Energy Volume LOOP 1 Supply temp Display test All on Power Flow LOOP 2 Accounting date Monthly date 1 Monthly date 12 LOOP...

Page 14: ...turn temperature Decimal emphasizer Temperature difference Units field 4 3 Alarms E01 System error E10 Transducer error E02 PCB error E11 Outside measured range E03 Battery empty less than 1 month E12...

Page 15: ...Module PCB 12 Bottom part PC 13 Temperature sensor 6 Disposal Item Material Disposal Battery AA cell Lithium thionyl chloride 620 mg Lithium Approved deposit for lithium batteries PCBA with display a...

Page 16: ...in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be...

Reviews: