4
Installation
1. Fix the wallplate to the wall or
fl
ush mounted box as
required. The connections are at the top and the
vertical centre line of the unit, at the position shown on
the diagram below C/L (in line with terminal )
2. Surface cables can only enter from below the unit. If
mounted on a
fl
ush mounted box, cables can enter
from the rear through the aperture in the wallplate.
3. For mains voltage applications a link must be
fi
tted
between terminals L, 2 and 5.
4. Whilst the unit does not require an Earth connection,
a terminal is provided on the wallplate for Earth
continuity
purposes.
Leave at
least 25mm
below
product
Rear entry
cable access
Cable aperture
knockouts
Wall or
plasterbox
fi
Terminal
block
Outline of
programmer
Leave suf
fi
cient space
for screwdriver access
C/L