ENGLISH

Thermostat type RT 106

Technical data 

Contact load: switch 017-4030, see fig. 9 
Enclosure: IP66 acc. to IEC 529 and EN60529 
Permissible ambient temperature: 
-50 °C – 70 °C
Maximum sensor temperature: 120 °C

 

Installation

A set of Pg13.5 cable gland is attached to 
the RT in a separate bag. To ensure IP66 
(units with automatic reset) or IP54 (units 
with external reset) grade of RT enclosure 
it is necessary to assemble this gland as 
shown in the fig. 2. If this gland is not used 
with a cable, a metal blinding should be 
also assembled.

RT units can be fitted in any position.
For correct fitting of bulb pockets. See fig. 1. 
See figs. 4, 6 and 9. 
Clip locating strip A (fig. 1) to length in 
accordance with fig. 3. 
with outdoor installation, the unit should 
be protected against direct rainfall. It 
could, for example, be placed under a 
lean-to roof.

Setting

Set the thermostat ( fig. 7) to the function 
required (make or break) on falling 
temperature. Read the setting on the main 
scale fig. 7. 

Example

 

An 

RT 106

 is required to regulate the 

temperature in an oil-fired central heating 
boiler. 

Maximum temperature: 55 °C 
Minimum temperature: 50 °C 
Differential: 55 °C - 50 °C = 5 °C

1.  Connect the oil burner to terminals 2–1
2.  Set the thermostate for 50 °C
3.  Set the differential adjusting nut  fig. 7 
  on number 3 which can be found by 
  reading of the nomogram in fig. 8.

A. Range setting 
B. Differential obtained 
C. Differential setting

DANSK

Termostat type RT 106

Tekniske data 

Kontaktbelastning: kontaktsystem 017-4030 
se figur 9 
Tæthed: IP66 acc. to IEC 529 and EN60529 
Tilladelig omgivelsestemperatur: 
-50 °C – 70 °C 
Max. følertemperatur: 120 °C

Montage

Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
DANSK RESET) er det nødvendigt at mon-
tere denne kabelforskruning som vist i fig. 2. 
Hvis denne kabelforskruning ikke bruges
sammen med et kabel, bør der monteres
en blindprop (metal skive).

RT apparaterne kan monteres vilkårligt med 
hensyn til position. 
Korrekt montage af føler i følerlomme, se 
figur 1. Iagttag figur 4, 6 og 9. 
Tilpas afstandsstrimlen A´s længde (figur 1) 
ved afklipning efter fig. 3. 
Ved udendørs montage, bør apparatet 
beskyttes mod direkte nedbør.Dette kan fx 
ske ved anbringelse under halvtag.

Indstilling

Indstil termostaten (se figur 7) til den
funktion - slutte eller bryde - som ønskes 
ved faldende temperatur. Aflæs indstilling 
på hovedskala fig. 7. 

Eksempel

Temperaturen i en oliefyret centralvarme-
kedel ønskes reguleret  af en 

RT 106

Max. temperatur: 55 °C 
Min. temperatur: 50 °C 
Differens: 55 °C - 50 °C = 5 °C

1.  Tilslut oliebrænderen til termostatens 
  klemmer 2–1
2.  Indstil termostaten på 50 °C
3.  Indstil differensrullen fig. 7 på tallet 3 
  som fremkommer ved aflæsning af 
  nomogrammet i figur 8.

A. Områdeindstilling 
B. Opnået differens 
C. Differensindstilling

DEUTSCH

Thermostat Typ RT 106

Technische Daten

Kontaktbelastung: kontaktsystem 017-4030, 
siehe Figur 9 
Schutzart: IP66 acc. to IEC 529 and EN60529 
ZulässigeUmgebungstemperatur: 
-50 °C – 70 °C 
Max. Fühlertemperatur: 120 °C

 

Montage

Die Kabelverschraubungen PG13,5 sind in
einem separaten Beutel verpackt. Zum
erreichen des IP66 Schutzgrades (Geräte
mit automatischen Reset) oder IP54 (Geräte 
mit externen Reset) ist eine Montage dies-
er Verschraubung notwendig, (siehe Abb. 
2.). Wenn diese Kabelverschraubung nicht 
benötigt wird ist ein Metall Blindstopfen zu 
verwenden.

Die RT-Geräte können in beliebiger 
Stellung montiert werden. Die korrekte 
Montage des Fühlers in die Fühlerhülse ist 
für Geräte ohne Kapillarrohrbewehrung in 
Fig. 1. 
Beachte Figur 4, 6 und 9. 
Die A-Länge des Abstandsstückes (Fig. 1) 
ist gem. Fig.3 abzuschneiden. Bei Montage 
im Freien sollte das Gerät gegen Nied-
erschläge geschützt werden, z.B. durch 
Anbringen unter einem Dachvorsprung. 

Einstellung

Der Thermostat (siehe Fig. 7) ist auf die 
Funktion - Ein oder Aus - einzustellen, die 
bei abfallender Temperatur gewünscht 
wird. DieEinstellung ist an der Hauptskala 
Fig. 7 abzulesen. 

Beispiel

 

Die Temperatur in einem ölbefeuerten 
Zentralheizungskessel soll von einem 

RT 106

 geregelt werden. 

Max. Temperatur: 55 °C 
Min. Temperatur: 50 °C 
Differenz: 55 °C - 50 °C = 5 °C

1.  Der Ölbrenner an die Klemmen 2–1 des 
  Thermostats anschliessen
2.  Der Thermostat ist auf 50oC einstellen
3.  Die Differenzrolle fig. 7 ist auf die Zahl 3 
  einzustellen, die auf dem nomogramm 
  in Fig. 8 abzulesen ist.

A. Bereichseinstellung
B. Erreichte Differenz
C. Differenzeinstellung