400-900MHz Receiver LED troubleshooting

The troubleshooting LEDs are located on the receiver board. Use the following table to identify faults and

corrective action.

In order to reach the signaling, the receiver must be accessible, connected, and the screws located on the
receiver lid must be unscrewed using the proper screw driver whenever the LEDs are not externally
visible.

The LEDs on the receiver board are POWER, HARDOK, SIGNAL, DATA, ID, ORDER and RELAY.

Please do check the following website for further information:

https://troubleshooting.dps-rct.com/en/customer-service-center

LED

Characteristic

Description

Action

POWER

Green; pulsing

Receiver is starting up

Wait until start-up process is

finished

HARDOK

Green; continuous

Receiver hardware OK

Operate

Red; pulsing

EEPROM error; data corruption; CAN bus error (if CANERR

activates)

Reprogram EEPROM

Red; other

Electronic board hardware breakdown

Replace device

SIGNAL

LED off

No radio signal detected

-

LED on + transmitter switched

off

Radio channel occupied

Change transmitter's frequency

channel

LED on + DATA switched off

Radio channel occupied by non Danfoss system

Change transmitter's frequency

channel

DATA

LED off + SINGAL LED on

Radio error

Replace radio

Green; pulse

Receiving good frames

OK

ID

LED off + DATA LED on

No valid ID; Danfoss system nearby

If channel not occupied, check

chosen ID in the transmitter or

reset the receiver

LED on + SIGNAL LED on +

DATA LED on

Valid frames received from the transmitter; correct link

OK

RELAY

Green

STOP relay activated

-

ORDER

Green

LED ON Whenever any output is ON

-

CANERR

Red | slow pulses

CAN Error, physical Layer

Verify Connections

Red | double pulses

One expansion has Stopped working

Verify Expansion boards

Red | 4 pulses

A Transmitted CAN frame has been lost

N/A

Red | 5 pulses

A Received CAN Frame has been lost

N/A

Red | continuous

CAN Bus OFF

Verify CAN connections and

Status.

CANRUN

Blinking Green

Pre operational Status

The Controller must set the CAN

Receiver to operational Status

Solid Green

Operational Status

OK

User Manual

R06 Receiver

Troubleshooting

 

10 | 

©

 Danfoss | March 2019

BC292460489593en-000201

Summary of Contents for R06

Page 1: ...User Manual Remote Control R06 Receiver www danfoss com ...

Page 2: ... of revisions Date Changed Rev March 2019 Updated safety information and technical description 0201 January 2019 Rebranded to Danfoss Power Solutions 0101 User Manual R06 Receiver 2 Danfoss March 2019 BC292460489593en 000201 ...

Page 3: ...ety warnings 5 Technical description Dimensions 6 Hardware description 7 R06 Detailed description 7 Installation Receiver installation 9 Troubleshooting R06 troubleshooting 10 User Manual R06 Receiver Contents Danfoss March 2019 BC292460489593en 000201 3 ...

Page 4: ...e de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement R06 General Safety The following safety instructions must be read carefully to install and use the product properly and to keep it in perfect working condition and to reduce the risk of misuse Strictly adhere to the installati...

Page 5: ... use Always press STOP before plugging in tether cable if applicable Remove the Tether connection on the transmitter First if applicable Do not operate product when visibility is limited Make sure product is compatible with the machine Avoid knocking or dropping the product Do not use the product if a failure is detected Changes or modifications not approved by Danfoss can void the user s authorit...

Page 6: ... 2 14 14 6 151 00 135 14 R 2 60 129 00 113 27 R 2 60 28 20 23 80 R 2 60 26 60 17 20 41 49 75 49 R 2 60 61 60 55 60 See next page for callout details User Manual R06 Receiver Technical description 6 Danfoss March 2019 BC292460489593en 000201 ...

Page 7: ... connection 9 BUS termination CAN 10 TR800CE MCX 11 Power supply 48 230 V 12 STOP relays 13 Maneuver relays 14 Internal multi band antenna R06 Detailed description Technical data Description Value Stop function 400 900MHz Cat 3 PLd Ingress Protection rating IP65 NEMA4 User Manual R06 Receiver Technical description Danfoss March 2019 BC292460489593en 000201 7 ...

Page 8: ...s 6 6A Proportional Outputs N A CAN Bus Protocols CANopen ON OFF inputs Option Analog inputs Option Response Time 100ms Maximum Total output current 8A Operating Temperature Range 20 C to 70 C 4 F to 158 F Storage Temperature Range 24h 25ºC to 75ºC 13ºF to 167ºF Storage Temperature Range long periods 25ºC to 55ºC 13ºF to 131ºF Relative Humidity max 95 without condensation Weight 640 grams Dimensio...

Page 9: ...n the receiver s antenna and the transmitter s working area it is recommended to use an extended antenna in a clear location only for models that allow an antenna In areas of high vibration the use of dampers is advised 3 Proceed to connect the power supply Use the connection block diagram provided with the system where the correspondence between the transmitter maneuvers and the receiver s output...

Page 10: ...ed LED on transmitter switched off Radio channel occupied Change transmitter s frequency channel LED on DATA switched off Radio channel occupied by non Danfoss system Change transmitter s frequency channel DATA LED off SINGAL LED on Radio error Replace radio Green pulse Receiving good frames OK ID LED off DATA LED on No valid ID Danfoss system nearby If channel not occupied check chosen ID in the ...

Page 11: ...Danfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading Shanghai Co Ltd Building 22 No 1000 Jin Hai Rd Jin Qiao Pudong New District Shanghai China 201206 Phone 86 21 2080 6201 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its prod...

Reviews: