Technical Information
Output Configurations for PLUS+1® Controllers
520L0922
• Rev EA • Sep 2013
7
Driving a Bidirectional
Proportional Valve
Option 1 – H bridge configuration for single coil
Certain output pin pairs may be set for the H bridge configuration. Please refer to the API
specification for the pinouts on a particular hardware. This is an open loop PWM configuration
(PinConfig = 7).
2299
Load
Ground
+Batt
Logic circuits
FET
H-bridge
Configuration
FET
Logic circuits
FET
FET
H-bridge
Configuration
Option 2 – closed loop current controlled configuration for single coil
You may also use two outputs configured for closed loop current control to drive a bi-directional
valve. Certain output pin pairs may be used for this configuration (PinConfig = 8). Set the current
command to the desired milliamps. Please refer to the API specification for the pinout pairs available
on a particular hardware.
2300
Load
Ground
+Batt
Logic circuits
FET
FET
Logic circuits
FET
FET
PWM Closed
Loop Current
Configuration
PWM Closed
Loop Current
Configuration