Closed Loop Set-up Wizard
6-29 Terminal 54 Mode
[1]
Voltage mode
6-25 Terminal 54 High Ref./Feedb. Value
0050
Hz
20-94 PI Integral Time
9999
s
Current
Voltage
This dialog is forced to be set to
[2] Analog in 54
24
25
26
27
28
29
30
31
20-00 Feedback1 source
[2]
Analog in 54
3-10 Preset reference [0]
[1]
0
3-03 Max Reference
[1]
50
3-02 Min Reference
[1]
0
Asynchronous Motor
1-73 Flying Start
[0]
No
1-22 Motor Voltage
50
V
1-24 Motor current
4.66
A
1-25 Motor nominal speed
1420
RPM
3-41 Ramp 1 ramp-up time
0003
s
3-42 Ramp1 ramp-down time
0003
s
3
4
5
6
7
13
14
15
17
18
18a
20
21
22
23
32
33
34
35
36
37
0-06 Grid Type
[200-240 V/50 Hz]
4-12 Motor speed low limit
0
Hz
4-14 Motor speed high limit
65
Hz
130BC245.10
1-20 Motor Power
1.10
kW
1-23 Motor frequency
50
Hz
6-22 Terminal 54 Low Current
4 mA
6-24 Terminal 54 Low Ref./Feedb. Value
0016
Hz
6-23 Terminal 54 High Current
20
mA
6-25 Terminal 54 High Ref./Feedb. Value
50
0,01
s
20-81 PI Normal/Inverse Control
[0]
Normal
20-83 PI Start Speed
0
Hz
20-93 PI Proportional Gain
0,01
s
1-29 Automatic Motor Adaption
[1]
Enable
6-20 Terminal 54 Low Voltage
0,07
V
6-24 Terminal 54 Low Ref./Feedb. Value
0
Hz
6-21 Terminal 54 High Voltage
10
V
6-26 Terminal 54 Filter time constant
3-10 Preset reference is the set-point
Please note that Terminal 27 Digital Input (par. 5-12)
has coast inverse as default setting. This means that
AMA can not be performed if there is no 24V to terminal
27 so please connect terminal 12 to terminal 27.
0-01 Configuration Mode
[0]
Open Loop
2
0-03 Regional Settings
[0]
International
1
3-16 Reference 2 Source
[0]
No function
20
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT
®
is a registered Danfoss trademark
17