Danfoss Optyma Trio Series Application Manual Download Page 14

Installation and Operation

4.3.1 Fixation

Figure 7

4.4 Leak detection

4.5 Vacuum dehydration

4.6 Electrical Installation

•  Never pressurize the circuit with oxygen or 

dry air. This can cause fire or explosion.

•  Do not use dye for leak detection.
•  The use of nitrogen or the system’s own gas 

is recommended.

•  Perform a leak detection test in the entire 

system.

• The maximum test pressure is 32 bar.
•  When a leak is detected, repair the leak 

and repeat the leak detection.

• Never use the compressor to empty the system.
•  Connect a vacuum pump to the system’s lower 

sides LP and HP.

•  The vacuum in the system must reach at least a 

complete 500 μm Hg (0.67 mbar).

•  When the vacuum level is reached, keep it for a 

few hours to guarantee the sealing of the system.

•  After this stage, isolate the vacuum pump and 

place the nitrogen with a pressure of 4 to 5 bar, 
keeping the system at this pressure for 4 hours. 

•  If the pressure in the gauge connected to the 

suction line and discharge lowers in this period, 
locate the leak, perform the repair and restart 
the vacuum procedure and check the leak again.

•  Do not apply energy to the unit while the 

system is under vacuum, as this might cause 
internal damage.

•  Switch off and isolate the main power supply.
•  Make sure that the power supply can’t be 

switched on accidentally during installation.

•  All the electrical components must be selected 

according to the local standards and according 
to the unit’s requirements.

•  Consult the wiring diagram supplied with the 

installation manual for details on electrical 
connections.

•  Make sure that the power supply matches the 

unit characteristics and that the energy source 
is stable (nominal voltage ± 10% and nominal 
frequency ± 2.5 Hz).

•  Dimension the power supply cables according 

to the unit data on voltage and current.

•  Protect the power supply and ensure that the 

grounding of the unit is done according to the 
current standards.

•  The unit is equipped with high and low pressure 

switches, which directly shut off the power 
supply to the compressor in case of activation. 
The unit is also equipped with a phase sequence 
relay to protect the unit against phase/ 
sequence loss / asymmetry and under voltage / 
over voltage.

•  Observe the correct phase sequence in the 

condensing units which use three-phase 
compressors. 

•  Determine the sequence using a phase gauge 

to establish the sequences of the line phases L1, 
L2 e L3.

•  Connect the line phases L1, L2 e L3 

corresponding to the terminals of the 
compressor T1, T2 e T3 respectively.

Fixation of 4 “vibra-stop” type shock 

absorbers included on the Danfoss 

supply for the support on the floor 

or laying base

14

FRCC.PC.053.A1.02

Application Guide

Summary of Contents for Optyma Trio Series

Page 1: ...Optyma Trio Application Guide http RA danfoss com br...

Page 2: ......

Page 3: ...5 Electrical Data 10 3 6 Dimensional Data 11 4 1 Storage and Handling 12 4 2 Precautions 12 Installation and Operation 12 4 3 Mechanical Installation 13 4 4 Leak detection 14 4 5 Vacuum dehydration 14...

Page 4: ...E Danfoss condenser Even though a lot of benefits for the use of in parallel compressor systems exist the more important benefits are the use of less equipment flexibility on the capacity control use...

Page 5: ...ironments and great diversity of dirt 6 pole motorized fans selected to assist in low noise level operations with dynamic balancing Designed for use in outdoor environments Designed for easy installat...

Page 6: ...ase 9 Service valve GBC liquid line 10 Service valve GBC suction line 11 Sight glass 12 Suction filters and liquid line 13 High and low security pressure switch 14 Fan s control pressure switch 15 Suc...

Page 7: ...ology D Micro channel 5 Productconfiguration Table 1 6 Electrical Codes Q 220V 3F 60Hz V 380V 3F 60Hz 1 2 3 4 5 6 H U D Q 5100 50 Code Application Pressure switch Liquid receiver Separator andoilreser...

Page 8: ...rs Information E Fans Information F HP pressure test G LP pressure test H Apparent power I Active power J RLA nominal current K Maximum current of MCC application Model Code Serial Fan 4 HP Pressure b...

Page 9: ...25 90 32180 26 58 39200 27 45 47170 28 47 56080 29 60 65900 30 79 76600 31 99 35 30490 27 98 37210 28 83 44830 29 84 53330 30 96 62720 32 14 72990 33 34 38 28840 28 43 35180 30 31 42430 31 30 50540 32...

Page 10: ...599 3 230V 3F 60Hz 123 0 16 7 26 0 500 4 6 380 230V 3F 60Hz 1 5 0 9 HU2900D50V 115F0556 24 03 380V 3F 60Hz 36 52 MLZ038T9 121U8591 3 380V 3F 60Hz 81 0 11 0 17 0 500 4 6 380 380V 3F 60Hz 1 5 0 9 HU3500...

Page 11: ...1485 2057 1368 1585 2157 1468 250 224 246 348 HU4500D50V 1485 2057 1368 1585 2157 1468 250 224 246 348 HU5100D50Q 1485 2057 1368 1585 2157 1468 250 224 246 348 HU5100D50V 1485 2057 1368 1585 2157 146...

Page 12: ...ust only be held by a certified installer engineer electrician and in accordance with the local regulatory guidelines Never place the unit in a flammable atmosphere Place the unit in a way that it doe...

Page 13: ...e the suction tubing with insulation thickness that meets the specific project conditions for the installation For the initial start up the oil level must be verified and completed with a parcial load...

Page 14: ...y Make sure that the power supply can t be switched on accidentally during installation All the electrical components must be selected according to the local standards and according to the unit s requ...

Page 15: ...e 5 Verify if the power supply is adequately connected Verify if the crankcase heater is working Verify if the fan can rotate freely Verify if high and low pressure are balanced Energize the unit and...

Page 16: ...maintenance records in the established conditions Check if all electrical connections still are properly attached Keep the unit clean and without rust and oxidation of the unit s components tubing and...

Page 17: ...060 117166 060 117166 060 117166 Condensing Units HU5100D50V LZ0012D50Q LZ0012D50V LZ0014D50Q LZ0014D50V LZ0018D50Q LZ0018D50V Accumulator 191U0068 191U0067 191U0067 191U0067 191U0067 191U0068 191U006...

Page 18: ...n feet and shock markings Open compressor or returned without sealing Dye for rust detection water or leak in the compressor Use of an off specification refrigerant or lubricant Any deviation from the...

Page 19: ...nds that gases oils and other components that can adversely affect the environment be delivered to dedicated companies in the recycling or disposal of those materials for environment protection 19 FRC...

Page 20: ...pressors which placed us among the global leaders in our business and positioned us as variable speed technology specialists Currently we act from the engineering and project up to the production stag...

Reviews: