Installation and Operation
To guarantee an adequate protection,
it is necessary to observe all emphasized
recommendations in this application guide.
The next sections will provide necessary
recommendations for the installation and
operation of the Optyma
TM
Trio unit, as well as
safety data and appropriate use of the product.
4.1 Storage and Handling
4.2 Precautions
• It is not recommended to open the packaging
before the unit being at the installation site.
• Handle the unit carefully. The framework
allows the use of a forklift or handling cart. Use
appropriate and safe elevation equipment.
• Keep the unit in a vertical position both in
storage and transport.
• Store the unit in an adequate and protected
environment.
• Do not expose the packaging to rain or
corrosive atmosphere.
• After unpacking, verify if the unit is complete
and undamaged.
All the equipment must be examined carefully
upon product receipt in order to verify if
no damages were caused by handling and
transportation.
This equipment was carefully inspected in
our factory, in case there is any apparent or
hidden malfunction, notify immediately the
establishment where it was purchased.
• The installation and maintenance of this unit
must only be held by a certified installer /
engineer / electrician and in accordance with
the local regulatory guidelines.
• Never place the unit in a flammable atmosphere
• Place the unit in a way that it doesn’t block or
complicate the passage areas, doors, windows,
stairs and other accesses.
• Ensure adequate space around the unit for
the air circulation and door opening. See figure
6 to obtain the minimum distance values to
the walls.
• Avoid installing the unit in aggressive
environments and with difficult access.
• Ensure a base with strong horizontal surface
that is stable enough to support all the
unit’s weight and eliminate the vibrations
by misalignment.
• Check if the power supply corresponds
to the technical specifications of the unit
(see product’s marking label).
• By installing units for HFC refrigerants, use
specific equipment for that type of refrigerant,
in other words, that have never been used
before for CFC or HCFC.
• The suction tubing must be flexible in 3 dimensions
to muffle the vibrations. Furthermore, the tubing
must be done in a way so that the return of the
oil to the compressor is ensured and the return of
liquid refrigerant to the compressor is avoided.
The installation at ground level rarely presents
problems, none the less, if it is not installed at
ground level, an additional tubing for drainage
must be considered in the project.
12
FRCC.PC.053.A1.02
Application Guide