background image

”unit” in the scope this directive. Under all circum-

stances local safety regulations must be fulfilled.

 •  The unit must be securely installed on a stable 

and rigid support, and fixed from the begin-

ning. See picture 2.

 • 

 It is recommended to install the unit on rub-

ber grommets or vibration dampers . 

Rubber 

pads with mounting bolts are supplied.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as possible 

to avoid oil contamination from ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 

insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 32 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  

Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply 

to the compressor in case of activation. Version 

W04 is also equipped with phase sequence relay 

to protect the unit against phase loss/sequence/ 

asymmetry and under-/over-voltage.

For units with a 3-phase scroll compressor, cor-

rect phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main swit-

ch terminals T1, T2 and T3 respectively.

8 – Filling the system

 •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A 

/ R507, R22 or R448A/R449A and approx. 2 bar 

for R134a.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices in compliance with both 

generally and locally applicable regulations and 

safety standards. 

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shut-down 

period.

10 – Start-up

 •  Never start the unit when no refrigerant is char-

ged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 •  Check that the protection sheet has been re-

moved from the backside of condenser.

 •  Balance the High Pressure / Low Pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

 •  Eventual reverse rotation of  a 3-phase com-

pressor can be detected by following phe-

nomena; unit doesn’t start, the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the unit 

immediately and connect the phases to their 

proper terminals.

 •  If the rotation direction is correct the low pres-

sure indication on the low pressure gauge shall 

show a declining pressure and the high pres-

sure indication on the high pressure gauge 

shall show an increasing pressure.

11 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow com-

pressed air through the coil from the inside out, 

and brush with a soft bristle. Do not use a wire 

brush. Do not impact or scrape the coil with the 

vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to be 

done, it shall be done in such a way that no refri-

gerant can escape to the environment.

13 - Warranty

Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

 •  Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or main-

tenance.

 •  Use in mobile applications.

 •  Use in explosive atmospheric environment.

 •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that condensing units and 

oil should be recycled by a suitable company at 

its site.

Instructions

2 |  © Danfoss | DCS (CC) | 2018.07

FRCC.PI.022.B0.02

Summary of Contents for Optyma Slim Pack OP-MPME048

Page 1: ...switch compressors contactor overload relay Crankcase heater OP LPHE units only 2 Handling and storage It is recommended not to open the packaging before the unit is at the final place for installation Handle the unit with care The packaging al lows for the use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between...

Page 2: ...e protection sheet has been re moved from the backside of condenser Balance the High Pressure Low Pressure Energize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence phase Eventual reverse rotation of a 3 phase com pressor can be detected by following phe nomena unit doesn t start the compressor doesn t build up pressure it h...

Page 3: ...OP LPHE067 084 098 OP MPUE068 080 093 099 108 OP LPHE048 068 OP MPUE034 046 057 OP MPME048 060 OP MPZE060 Instructions Danfoss DCS CC 2018 07 3 FRCC PI 022 B0 02 ...

Page 4: ...o LP auto LP man HP man HP man HP auto HP auto P H t e s e r n a m P L t e s e r t u a P L AC1 16 A DC 11 LR 112A AC3 16 A 400 V 12 W AC1110 A 220 V When used acc to UL regulations 1 bar Pe 30in Hg Convertible reset KP 15 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Instructions 4 Danfoss DCS CC 2018 07 FRCC PI 022 B0 02 ...

Page 5: ...PRESSOR M T1 T3 T2 3 M1 BU 11 FAN SPEED CONTROLLER P 2 1 B3 BN 12 BN 034 046 069 081 cm 3 DISPLACEMENT 108 048 061 SOLENOID VALVE A1 A2 Y1 BK GY MLZ compr CRANKCASE HEATER MT compr BN BU BN BU 2 1 E1 2 1 E1 Option Q1 F1 K3 K2 S1 T T S2 K3 K2 BN BU P P HIGH PRESSURE LOW PRESSURE B C A D PE B2 MODEL COMPRESSOR MLZ015T4LP9 MLZ021T4LP9 MLZ030T4LC9 MLZ038T4LC9 MLZ048T4LC9 MLZ045T4LC9 MT28 4VM MT36 4VM ...

Page 6: ...2 PE B1 A1 A2 PE Y1 10 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 PE X1 2 1 E1 M 1 M2 setting Einstellung ajustage F2 Code BK BN GY PE X1 M 1 S C R M1 C2 WH C1 R1 RD 5 2 1 5 K2 230V1N 50Hz L PE N BN F1 BU 1 2 3 4 5 6 K1 xxA 5 6 3 4 1 2 F2 BU BN BU R2 BN value Wert valeur Bereich range domaine type Typ type P P B C A D PE B2 PE X1 7 BN BN BU BU S C R 114X7042 114X7044 114X7046 OP MPUE068MLW04G ...

Page 7: ...eversal protection relay B1 Fan Speed Controller B2 DUAL Pressure Switch B3 Low pressure switch C1 Start capacitor compressor C2 Run capacitor compressor E1 Crankcase heater F1 Main switch F2 Overload relay F3 Fuse control circuit M1 Compressor M2 Fan motor K1 Contactor K2 Start relay R1 R2 Bleeder resistor S1 Room thermostat X1 Terminals Y1 Solenoid valve S1 Instructions Danfoss DCS CC 2018 07 7 ...

Page 8: ...r M2 Fan motor K1 Contactor K2 Start relay R1 R2 Bleeder resistor S1 Room thermostat X1 Terminals Y1 Solenoid valve 8 Danfoss DCS CC 2018 07 FRCC PI 022 B0 02 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alt...

Reviews: