 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

 Under all circumstances, the EN378 (or  

other applicable local safety regulation) 

requirements must be fulfilled.

The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation»

 

section for further details. 
The condensing unit must be handled with cau-

tion in the vertical position (maximum offset 

from the vertical : 15°)

MADE IN INDIA

OP-MPUE034MLW04E

Code no.:

Application

Refrigerant

M.W.P. HP

114X7039

MBP

(1) 

R404A, R507, R22, R448A, R449A

(1) 28 bar

             LP (1)  7  bar

IP54

(2) R134a

(2) 23 bar

(2)  5  bar

Voltage

380-400V3N~/50Hz

LRA

30,5

7,5

MCC

Serial No.

Barcode Serial No: 

123456CG0514

118UXXXX

A

B

C

D

E
F

G

K

H

I

J

Installation and servicing of the 

condensing units by qualified 

personnel only. Follow these 

instructions and sound refrigeration 

engineering practice relating to installation, 

commissioning, maintenance and service.

A

:   Model

B

:   Code  number 

C

:   Application,  Protection

D

:   Refrigerant 

E

:   Housing Service Pressure

F

:   Supply voltage, Locked Rotor Ampere,  

Maximum Current Consumption

G

:   Serial Number and bar code

H

:   Cable entry ports

I

:   Suction  port

J

:   Liquid  port

K

:   Microchannel heat exchanger

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Picture 2 

Picture 3 

Mounting bolts 

1 – Introduction

These instructions pertain to Optyma

TM

 Slim 

Pack condensing units OP-LPHE/MPUE/MPME 

(R22, R404A, R507, R134a, R448A, R449A)) used 

for refrigeration systems. They provide necessa-

ry information regarding safety and proper usage 

of this product.

The condensing unit includes following:

version W02

  •  Scroll/reciprocating  compressor

 •  Microchannel heat exchanger

 •  Dual pressure switches

 •  Service valves suction/ liquid

 •  Weather proof housing

  •  Filter  drier

 •  Receiver with stop valve

  •  Sight  glass

  •  Solenoid  valve

version W04

 (without solenoid valve) includes also:

 •  Phase sequence relay 

 •  Fully pre-wired electrical panel (including main 

switch, compressors contactor, overload relay)

 •  Crankcase heater (OP-LPHE units only)

2 – Handling and storage

 •  It is recommended not to open the packaging 

before the unit is at the final place for installation.

 •  Handle the unit with care. The packaging al-

lows for the use of a forklift or pallet jack. Use 

appropriate and safe lifting equipment. 

 •  Store and transport the unit in an upright position.

 •  Store the unit between -35°C and 50°C.

 •  Don’t expose the packaging to rain or corrosive 

atmosphere.

 •  After unpacking, check that the unit is com-

plete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 

 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.

 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture1 

for minimal values of distance to walls.

 •  Avoid installing the unit in locations which are daily 

exposed to direct sunshine for longer periods.

 •  Avoid installing the unit in aggressive and dus-

ty environments.

 •  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable enough 

to carry the entire unit weight and to eliminate 

vibrations and interference.

 •  The unit ambient temperature may not exceed 

50°C during off-cycle.

 •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

 •  When installing units for HFC refrigerants, use 

equipment specifically reserved for HFC refri-

gerants which was never used for CFC or HCFC 

refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 •  The suction piping connected to the compres-

sor must be flexible in 3 dimensions to dampen 

vibrations. Furthermore piping has to be done 

in such a way that oil return for the compres-

sor is ensured and the risk of liquid slug over in 

compressor is eliminated.

4 – Installation

 •  The installation in which the condensing unit is ins-

talled must comply to EEC Pressure directive (PED) 

no. 2014/68/EU. The condensing unit itself is not a 

Instructions

Optyma™

 

Slimpack 

OP-LPHE/MPUE/MPME

1 | © Danfoss | DCS (CC)| 2018.07

FRCC.PI.022.B0.02

Summary of Contents for Optyma Slim Pack OP-MPME048

Page 1: ...switch compressors contactor overload relay Crankcase heater OP LPHE units only 2 Handling and storage It is recommended not to open the packaging before the unit is at the final place for installation Handle the unit with care The packaging al lows for the use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between...

Page 2: ...e protection sheet has been re moved from the backside of condenser Balance the High Pressure Low Pressure Energize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence phase Eventual reverse rotation of a 3 phase com pressor can be detected by following phe nomena unit doesn t start the compressor doesn t build up pressure it h...

Page 3: ...OP LPHE067 084 098 OP MPUE068 080 093 099 108 OP LPHE048 068 OP MPUE034 046 057 OP MPME048 060 OP MPZE060 Instructions Danfoss DCS CC 2018 07 3 FRCC PI 022 B0 02 ...

Page 4: ...o LP auto LP man HP man HP man HP auto HP auto P H t e s e r n a m P L t e s e r t u a P L AC1 16 A DC 11 LR 112A AC3 16 A 400 V 12 W AC1110 A 220 V When used acc to UL regulations 1 bar Pe 30in Hg Convertible reset KP 15 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Instructions 4 Danfoss DCS CC 2018 07 FRCC PI 022 B0 02 ...

Page 5: ...PRESSOR M T1 T3 T2 3 M1 BU 11 FAN SPEED CONTROLLER P 2 1 B3 BN 12 BN 034 046 069 081 cm 3 DISPLACEMENT 108 048 061 SOLENOID VALVE A1 A2 Y1 BK GY MLZ compr CRANKCASE HEATER MT compr BN BU BN BU 2 1 E1 2 1 E1 Option Q1 F1 K3 K2 S1 T T S2 K3 K2 BN BU P P HIGH PRESSURE LOW PRESSURE B C A D PE B2 MODEL COMPRESSOR MLZ015T4LP9 MLZ021T4LP9 MLZ030T4LC9 MLZ038T4LC9 MLZ048T4LC9 MLZ045T4LC9 MT28 4VM MT36 4VM ...

Page 6: ...2 PE B1 A1 A2 PE Y1 10 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 PE X1 2 1 E1 M 1 M2 setting Einstellung ajustage F2 Code BK BN GY PE X1 M 1 S C R M1 C2 WH C1 R1 RD 5 2 1 5 K2 230V1N 50Hz L PE N BN F1 BU 1 2 3 4 5 6 K1 xxA 5 6 3 4 1 2 F2 BU BN BU R2 BN value Wert valeur Bereich range domaine type Typ type P P B C A D PE B2 PE X1 7 BN BN BU BU S C R 114X7042 114X7044 114X7046 OP MPUE068MLW04G ...

Page 7: ...eversal protection relay B1 Fan Speed Controller B2 DUAL Pressure Switch B3 Low pressure switch C1 Start capacitor compressor C2 Run capacitor compressor E1 Crankcase heater F1 Main switch F2 Overload relay F3 Fuse control circuit M1 Compressor M2 Fan motor K1 Contactor K2 Start relay R1 R2 Bleeder resistor S1 Room thermostat X1 Terminals Y1 Solenoid valve S1 Instructions Danfoss DCS CC 2018 07 7 ...

Page 8: ...r M2 Fan motor K1 Contactor K2 Start relay R1 R2 Bleeder resistor S1 Room thermostat X1 Terminals Y1 Solenoid valve 8 Danfoss DCS CC 2018 07 FRCC PI 022 B0 02 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alt...

Reviews: