background image

1 – Introduction

These instructions pertain to Optyma

TM

 Slim Pack 

condensing units OP-LPQE/MPJE(R22, R404A, 
R507, R134a, R513A, R448A, R449A, R452A) used 
for refrigeration systems. They provide necessary 
information regarding safety and proper usage of 
this product.
The condensing unit includes following:
  •  Scroll/reciprocating  compressor
 •  Microchannel heat exchanger
 •  Dual pressure switches
 •  Service valves suction/ liquid
 •  Weather proof housing (IP 54)
  •  Filter  drier
 •  Receiver with stop valve
  •  Sight  glass
  •  Solenoid  valve
 •  Phase sequence relay *

)

 •  Fully pre-wired electrical panel (including main 

switch, compressors contactor, overload relay)

 •  Crankcase heater (OP-LPQE units in W12)*

)

*

)

 Refer version control for components details in all 

versions

2 – Handling and storage

 •  It is recommended not to open the packaging 

before the unit is at the final place for installation.

 • 

 

Handle the unit with care. The packaging 
allows for the use of a forklift or pallet jack. Use 
appropriate and safe lifting equipment. 

 •  Store and transport the unit in an upright position.
 •  Store the unit between -35°C and 50°C.
 •  Don’t expose the packaging to rain or corrosive 

atmosphere.

 •  After unpacking, check that the unit is complete 

and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 
 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.
 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture1 
for minimal values of distance to walls.

 •  Avoid installing the unit in locations which are daily 

exposed to direct sunshine for longer periods.

 •  Avoid installing the unit in aggressive and dusty 

environments.

 •  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable enough 
to carry the entire unit weight and to eliminate 
vibrations and interference.

 •  The unit ambient temperature may not exceed 

50°C during off-cycle.

 •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

 • 

 

When installing units for HFC refrigerants, 
use equipment specifically reserved for HFC 
refrigerants which was never used for CFC or 
HCFC refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.
 •  The suction piping connected to the compressor 

must be flexible in 3 dimensions to dampen 
vibrations. Furthermore piping has to be done 
in such a way that oil return for the compressor 
is ensured and the risk of liquid slug over in 
compressor is eliminated.

4 – Installation

 •  The installation in which the condensing unit is 

installed must comply to EEC Pressure directive 
(PED) no. 2014/68/EU. The condensing unit itself 
is not a ”unit” in the scope this directive. Under all 
circumstances local safety regulations must be 
fulfilled.

 •  The unit must be securely installed on a stable 

and rigid support, and fixed from the beginning. 
See picture 2.

 • 

 It is recommended to install the unit on rubber 
grommets or vibration dampers . 

Rubber pads 

with mounting bolts are supplied.

 •  

Slowly release the nitrogen holding charge 
through the schrader port.

 •  Connect the unit to the system as soon as possible to 

avoid oil contamination from ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 

• 

 

Braze with great care using state-of-the-art 
technique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control devices. 

When the schrader port is used for this, remove 
the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 
insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.
 •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 31 bar.
 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.
 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power to 

the compressor while it is under vacuum as this 
may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.
 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 

• 

 

Refer to wiring diagram for electrical 
connections details.

 •  Ensure that the power supply corresponds to 

the unit characteristics and that the power 
supply is stable (nominal voltage ±10% and 
nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  

Make the power supply according to local 
standards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply 
to the compressor and provides 230V a.c. 
alarm signals (max.50VA) in case of activation. 
Is also equipped with phase sequence relay to 
protect the unit against phase loss/sequence/ 
asymmetry and under-/over-voltage.

For units with a 3-phase scroll compressor, 
correct phase sequence for compressor rotation 
direction shall be observed.
 •  Determine the phase sequence by using a phase 

meter in order to establish the phase orders of 
line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main 

switch terminals T1, T2 and T3 respectively.

 DGT protection is required if the high and 

low pressure switch settings do not protect 
the compressor against operations beyond its 
specific application envelope. Please refer to 
the examples below, which illustrate where DGT 
protection is required (n°1) and where it is not 
(n°2). 
The compressor must not be allowed to cycle 
on the discharge gas thermostat. Continuous 
operations beyond the compressor’s operating 
range will cause serious damage to the 

Picture 2 

Mounting bolts 

Picture 3 

Anticlockwise (open)

Clockwise (Close)

Schrader valve

Instructions

2 |  AN363632996018en-ZA0201 - 118A2220B

© Danfoss | DCS (CC) | 2021.04

Summary of Contents for Optyma Slim Pack OP-LPQE Series

Page 1: ...E F G A Model B Code number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact v...

Page 2: ...toinstalltheunitonrubber grommets or vibration dampers Rubber pads with mounting bolts are supplied Slowly release the nitrogen holding charge through the schrader port Connecttheunittothesystemassoon...

Page 3: ...er towards the fan Check current draw and voltage Check suction superheat to reduce risk of slugging When a sight glass is provided observe the oil level at start and during operation to confirm that...

Page 4: ...507 R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 17 Dual Pressure switch Refrigerant setting Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF R134a R513A R1234y...

Page 5: ...signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP...

Page 6: ...E067 084 098 OP MPJE068 080 093 099 108 OP LPQE048 068 OP MPJE034 046 057 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 6 AN363632996018en ZA0201 118A2220B Danfoss DCS CC 20...

Page 7: ...W12G OP LPQE048NTW12G OP LPQE068NTW12G Code E version W12 OP MPJE034 046 057 OP LPQE048 068 WD2 114X7265 114X7255 114X7257 OP MPJE034MLW12G OP LPQE048NTW12G OP LPQE068NTW12G Code G version W12 OP MPJE...

Page 8: ...an motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Leg...

Reviews: