background image

compressor!

Discharge line

Thermostat

Bracket

Insulation

A DGT accessory is available from Danfoss: refer 
to section “Spare parts & accessories”.

8 – Safety

Fusible Plug is not available in unit, it is replaced 
with adapter plug. 
Unit has liquid receiver with an Adapter Plug with 
3/8” NPT connection. installer/end user can select 
various options as mentioned in EN378-2 : 2016 
Article § 6.2.2.3
 •  Optyma Slim Pack (W12 version only)  fitted 

with atmospheric pressure relief valve. Don’t 
connect any tube at end of the pressure relief 
valve.

 •  Optyma Slim Pack (W12 version only) factory 

fitted with pressure relief valve at 33 bar setting.

 •  Once the pressure relief valve opens, don’t use 

dry air or oxygen to evacuate.

 

• 

 

Once pressure relief valve opens, Danfoss 
recommended to replace new pressure relief 
valve.

 •  The unit/installation into which the condensing 

unit is mounted/integrated, must be in 
accordance with the PED.

 •  Beware of hot and extremely cold components.
 •  Beware of moving components. Power supply 

should be disconnected while servicing.

9 – Filling the system

 •  Wear protective stuff like goggles and protective 

gloves.

 •  Never start the compressor under vacuum. Keep 

the compressor switched off.

 •  Before charging the refrigerant, verify that the oil 

level is between ¼ and ¾ on the compressor oil 
sight glass. If additional oil is required please refer 
to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  

Fill the refrigerant in liquid phase into the 
condenser or liquid receiver. Ensure a slow 
charging of the system to 4 – 5 bar for R404A / 
R507, R22, R452A or R448A/R449A and approx. 2 
bar for R134a and R513A.

 •  Do not put liquid refrigerant through suction line.
 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 

• 

 

The remaining charge is done until the 
installation has reached a level of stable nominal 
condition during operation.

 •  Never leave the filling cylinder connected to the 

circuit.

10 – Verification before commissioning

 Use safety devices in compliance with both 

generally and locally applicable regulations and 
safety standards. 
 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-up 
and start-up after prolonged shut-down period.

11 – Start-up

 •  Never start the unit when no refrigerant is 

charged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.
 •  Check that the fan can rotate freely.
 • 

 

Check that the protection sheet has been 
removed from the backside of condenser.

 •  Balance the High Pressure / Low Pressure.
 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 
conformity, voltage on terminals and sequence 
phase.

 

• 

 

Eventual reverse rotation of  a 3-phase 
compressor can be detected by following 
phenomena; unit doesn’t start, the compressor 
doesn’t build up pressure, it has abnormally 
high sound level and abnormally low power 
consumption. In such case, shut down the unit 
immediately and connect the phases to their 
proper terminals.

 •  

If the rotation direction is correct the low 
pressure indication on the low pressure gauge 
shall show a declining pressure and the high 
pressure indication on the high pressure gauge 
shall show an increasing pressure.

12 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.
 • 

 

Check suction superheat to reduce risk of 
slugging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 
that the oil level remains visible.

 •  Respect the operating limits.
 

• 

 

Check all tubes for abnormal vibration. 
Movements in excess of 1.5 mm require 
corrective measures such as tube brackets.

 •  

When needed, additional refrigerant in liquid 
phase may be added in the low-pressure side 
as far away as possible from the compressor. 
The compressor must be operating during this 
process.

 •  Do not overcharge the system.
 •  Never release refrigerant to atmosphere.
 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 
future inspections.

13 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature are 

dangerous and may cause permanent injury.
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.
To prevent system related problems, following
Periodic  maintenance is recommended:
 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.
 •  Check the compressor current draw.
 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 
tubes and electrical connections.

The condenser must be checked at least once 
a year for clogging and be cleaned if deemed 
necessary. Access to the internal side of the 
condenser takes place through the fan panel. 
Microchannel coils tend to accumulate dirt on 
the surface rather than inside, which makes them 
easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before remove 

any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 
other soft attachment. Alternatively, blow 
compressed air through the coil from the inside 
out, and brush with a soft bristle. Do not use a 
wire brush. Do not impact or scrape the coil with 
the vacuum tube or air nozzle.

If the refrigerant system has been opened, the 
system has to be flushed with dry air or nitrogen 
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to 
be done, it shall be done in such a way that no 
refrigerant can escape to the environment.

14 - Warranty

Always transmit the model number and serial 
number with any claim filed regarding this product.
The product warranty may be void in following 
cases:
 •  Absence of nameplate.
 •  

External modifications; in particular, drilling, 
welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.
 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved by 

Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or 
maintenance.

 •  Use in mobile applications.
 •  Use in explosive atmospheric environment.
 •  No model number or serial number transmitted 

with the warranty claim.

15 – Disposal

Danfoss recommends that condensing 
units and oil should be recycled by a 
suitable company at its site.

Instructions

 118A2220B - AN363632996018en-ZA0201 | 3

© Danfoss | DCS (CC) | 2021.04

Summary of Contents for Optyma Slim Pack OP-LPQE Series

Page 1: ...E F G A Model B Code number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact v...

Page 2: ...toinstalltheunitonrubber grommets or vibration dampers Rubber pads with mounting bolts are supplied Slowly release the nitrogen holding charge through the schrader port Connecttheunittothesystemassoon...

Page 3: ...er towards the fan Check current draw and voltage Check suction superheat to reduce risk of slugging When a sight glass is provided observe the oil level at start and during operation to confirm that...

Page 4: ...507 R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 17 Dual Pressure switch Refrigerant setting Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF R134a R513A R1234y...

Page 5: ...signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP...

Page 6: ...E067 084 098 OP MPJE068 080 093 099 108 OP LPQE048 068 OP MPJE034 046 057 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 6 AN363632996018en ZA0201 118A2220B Danfoss DCS CC 20...

Page 7: ...W12G OP LPQE048NTW12G OP LPQE068NTW12G Code E version W12 OP MPJE034 046 057 OP LPQE048 068 WD2 114X7265 114X7255 114X7257 OP MPJE034MLW12G OP LPQE048NTW12G OP LPQE068NTW12G Code G version W12 OP MPJE...

Page 8: ...an motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Leg...

Reviews: