Installation and servicing of the conden-

sing units by qualified personnel only. 

Follow these instructions and sound refri-

geration engineering practice relating to 

installation, commissioning, maintenance 

and service.

 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

 Under all circumstances, the EN378 (or  

other applicable local safety regulation) 

requirements must be fulfilled.

The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation»

 

section for further details. 

The condensing unit must be handled with cau-

tion in the vertical position (maximum offset 

from the vertical : 15°)

MADE IN INDIA

OP-MPJE034MLW04E

Application

Refrigerant

M.W.P. HP

114X7039

MBP

(1) R404A, R507, R22, 

     R448A, R449A, R452A

(1) 28 bar

             LP (1)  7  bar

IP54

(2) R134a, R513A

(2) 23 bar

(2)  5  bar

Voltage

380-400V3N~/50Hz

LRA

OIL INSIDE   POE 46

30.5 A

7.5 A

MCC

Serial No.

EAN No.

Danfoss A/S, 6430 Nordborg, Denmark

Barcode Serial No: 

123456CG0514

XXXXXXXXXXX

118UXXXX

A
B
C

D
E
F

G

A

:   Model

B

:   Code  number 

C

:   Application,  Protection

D

:   Refrigerant 

E

:   Housing Service Pressure

F

:   Supply voltage, Locked Rotor Ampere,  

Maximum Current Consumption

G

:   Serial Number and bar code

* For exact values please refer name plate in unit

Name plate

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Designation system for the 

Optyma

™ Slim Pack range

    OP-MPJE  

034   ML  W12    E

1 2 3 4

5

6

7

8

1

Application

 

M = MBP 
L = LBP

2

Package

 

P = Packaged unit

3

Refrigerant

 

J  = R22/R134a/R513A/R404A/R448A/R449A/R452A
Q = R404A/R507/R452A

4

Condenser

 

E: Extreme and tropical ambient conditions up to 48°C

5

Swept volume

 

Swept volume in CC

6

Compressor platform

 

ML = MLZ (Scroll)
NT = NTZ (Reciprocating)
LL = LLZ (Scroll)

7

Version 

See version control table

8

Voltage code 

G = Compressor 230V/1N~/50Hz, fan 230V/1~/50Hz
E = Compressor 400V/3N~/50Hz, fan 230V/1~/50Hz

Optyma™ 

Slim Pack

W12

Service valves

Receiver

Filter drier

Sight Glass

Cranckase Heater (Only for LBP models)

Full Ebox

Fan speed controller (Provision only)

-

Dual Pressure switch KP

HP alarm provision

LP alarm Provision

Discharge gas thermostat provision

Pressure relief valve

7. Version control

Instructions

Optyma™

 

Slim Pack 

OP-LPQE/MPJE

© Danfoss | DCS (CC) | 2021.04

118A2220B - AN363632996018en-ZA0201 | 1 



Summary of Contents for Optyma Slim Pack OP-LPQE Series

Page 1: ...E F G A Model B Code number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact v...

Page 2: ...toinstalltheunitonrubber grommets or vibration dampers Rubber pads with mounting bolts are supplied Slowly release the nitrogen holding charge through the schrader port Connecttheunittothesystemassoon...

Page 3: ...er towards the fan Check current draw and voltage Check suction superheat to reduce risk of slugging When a sight glass is provided observe the oil level at start and during operation to confirm that...

Page 4: ...507 R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 17 Dual Pressure switch Refrigerant setting Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF R134a R513A R1234y...

Page 5: ...signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP...

Page 6: ...E067 084 098 OP MPJE068 080 093 099 108 OP LPQE048 068 OP MPJE034 046 057 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 6 AN363632996018en ZA0201 118A2220B Danfoss DCS CC 20...

Page 7: ...W12G OP LPQE048NTW12G OP LPQE068NTW12G Code E version W12 OP MPJE034 046 057 OP LPQE048 068 WD2 114X7265 114X7255 114X7257 OP MPJE034MLW12G OP LPQE048NTW12G OP LPQE068NTW12G Code G version W12 OP MPJE...

Page 8: ...an motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Leg...