background image

Instructions

8 | © Danfoss | DCS (CC) | 2018.07

FRCC.PI.059.A1.02

• Check that all safety devices are operational 
and properly set (safety pressure switch set 
point, mechanical relief valve if necessary, etc.). 
Make sure that these devices comply with both 
generally - and locally - applicable regulations 
and standards (e.g. EN 378-2:2016).

• When using high-pressure switches or relief 
valves, the setting must not exceed maximum 
service pressure of any system component. Re-
fer to the Application Guidelines for relevant 
condensing unit pressure safety limits.

• A low-pressure switch is recommended to 
prevent operation under vacuum. Use a mini-
mum setting of 1.2 bar (absolute).

• Verify that all electrical connections are proper-
ly fastened and in compliance with local safety 
regulations.

• A compressor crankcase heater is factory ins-
talled, ensure that it has been energized for a 
minimum of 12 hours before initial start-up and/
or during prolonged shutdown periods.

10 - Start up

 Never start the compressor in the absence of 

a refrigerant charge. 

• Do not bypass the LP or any other safety swit-
ches during start-up

• Check current draw and voltage levels.

• Monitor the oil sight glass to ensure proper oil 
return to the compressor.After 2 to 4 hours of 
operations under established conditions, check 
the oil level and add oil if necessary (refer to TI 
bulletin 3-025).
If oil return continues to perform poorly, further 
investigation of the piping design is required. 

• In all cases, the application limits of the compressor 
must be respected; moreover, high superheat values 
lead to high discharge temperatures and decrease 
compressor capacity. The maximum discharge tem-
perature is 130°C: operating at a higher temperature 
may result in refrigerant decomposition.

• Under steady-state operating conditions, check 
refrigerant piping or capillary tubes for abnor-
mal vibrations (refrigeration line movement in 
excess of 1.5 mm necessitates corrective actions, 
pipe brackets, etc.).

• Ensure that refrigerant flow through the liquid 
line sight glass (when mounted) is adequate and 
that operating temperatures correspond with 
system specifications.

• When needed, refrigerant may be added in the 
liquid phase, carefully throttling the refrigerant 
on the low-pressure side and as far as possible 
from the compressor.The compressor must be 
operating during this process.

 Do not overcharge the system.

11 - Troubleshooting

• 

Compressor failure to start:

 verify that the 

compressor is hooked up to the power supply; 
check the power lead connections and all sui-
table capacitors on single-phase models. If these 

verifications reveal no abnormality, control the 
motor windings with an ohmmeter. 

Note: when the internal motor protector has 
tripped out, it may take up to several hours to 
reset and restart the compressor.

• Compressor failure to build up pressure:

 

check to make sure that all bypass valves in the 
system have not been opened. Also check that 
all solenoid valves are in their proper position. 
If the internal pressure relief valve is open, the 
compressor sump will be warm and the com-
pressor will trip out on the motor protector. If 
this happens, it may take up to 2 or 3 hours to 
reset and automatically restart the compressor.

• Abnormal running noise on the system: 

  - Ensure the absence of any liquid flood-back 
to the compressor by means of measuring the 
return gas superheat and compressor sump 
temperature. The sump should be at least 10K 
above the saturated suction temperature under 
steady-state operating conditions.
  - Check that the fans are running free and wit-
hout vibration.

• The high-pressure switch trips out:

 check 

condenser operations (condenser cleanliness, 
fan operations, etc.). If above check out OK, the 
problem may be due to either refrigerant over-
charging or the presence of a non-condensable 
(e.g. air, moisture) in the circuit. 

• The low-pressure switch trips out:

 check eva-

porator operations (coil cleanliness, fan opera-
tions, water flow, water filter, etc.), liquid refrige-
rant flow and pressure drops (solenoid valve, filter 
dryer, expansion valve, etc.), refrigerant charge.

• Low refrigerant charge:

 the correct refrige-

rant charge is given by the liquid sight glass 
indication, the condenser delta T in relation to 
the refrigerant pressure tables (pressure-tempe-
rature), the superheat and the sub-cooling, etc. 
(if additional charge is deemed necessary, refer 
to the 

«Filling the system»

 section). 

• Compressor maximum short cycling: 

there 

must be a minimum delay of five minutes 
between two compressor starts. DCC recom-
mends the compressor should run at least two 
minutes after each start, and between each stop 
and start must be three minutes standstill. Only 
during pump down cycle, the compressor may 
run much shorter until the pumpdown pressure 
has been reached or when safety devices will 
prohibit compressor further operation.

12 - Maintenance

• Proper operations and maintenance of the 
condensing units serve to prevent against sys-
tem-related problems.The following preventive 
maintenance checks, to be performed at regular 
intervals, are highly recommended:

  - Control operating conditions (evaporating 

temperature, condensing temperature, com-

pressor discharge temperature, temperature 

difference on heat exchangers, superheat, 

sub-cooling). These conditions must always re-

main within compressor operation limits.

  - Verify that safety devices are operational and 

properly set.

  - Check the compressor oil level and quality; 

this step may include an acid test, humidity 

check, spectrometer analysis, etc. whenever the 

oil becomes discolored.

  - Ensure that the circuit is leak tight.

  - Verify the proper operation of heat exchan-
gers and, if necessary, clean them.
  - Check that the fans are running free (without 
vibration) and current draw on the compressor 
motor as well as proper voltage balance between 
phases.
  - Note 1: The condenser must be checked at 
least once a year for clogging and be cleaned if 
deemed necessary. Access to the internal side of 
the condenser takes place through the fan pa-
nel.
Microchannel coils tend to accumulate dirt on 
the surface rather than inside, which makes 
them easier to clean than fin-&-tube coils.
  - Change the filter dryer when necessary.
  - Check that all electrical connections are still 
adequately fastened. 
  - Make sure the condensing unit is clean and 
in good working order; verify the absence of rust 
or corrosion on components under pressure and 
electrical connections. 
  - Make sure the refrigerant charge is suitable 
for both winter and summer operation.
• Ensure that periodic in-service inspections re-
quired by local regulations are performed. 
  - Note 2: Remove surface dirt, leaves, fibers, 
etc. with a vacuum cleaner, equipped with a 
brush or other soft attachment. Alternatively, 
blow compressed air through the coil from the 
inside out, and brush with a soft bristle.
Do not use a wire brush. Do not impact or scrape 
the coil with the vacuum tube or air nozzle.

13 - Replacement

 Precaution must be taken when disconnec-

ting any components, cutting or drilling holes in 
the tubing to ensure that no refrigerant under 
pressure is present in the system.

 The refrigerant shall not be discharged direc-

tly into the atmosphere; rather, it must be remo-
ved using approved reclamation techniques and 
equipment and then safely stored, inaccordance 
with applicable legislation.

 The presence of refrigerant vapor can displace 

air and lead to suffocation. Proper ventilation is 
mandatory at all times when servicing the equip-
ment.

 A condensing unit component change must be 

carried out in compliance with local regulations.

• Make sure that the main power supply has 
been switched off.

• Before replacement, it is necessary to deter-
mine the cause of failure and implement reme-
dial action. If such analysis and repair are not 
performed, repetitive failure may occur. Note 
that an oil acidity test always proves helpful in-
diagnosis when undertaking compressor repla-
cement.

• Check that the replacement component has 
the same electrical and refrigeration perfor-
mance characteristics as the original one.

Summary of Contents for Optyma OP-LCQN048

Page 1: ... MTZ050 MTZ056 MTZ064 MTZ072 MTZ080 836 5 1200 800 OP MGRN108 OP MGRN121 OP MGRN136 MTZ064 MTZ072 MTZ080 693 5 1500 870 OP MGRN171 OP MGRN215 OP MGRN242 OP MGRN271 MTZ100 MTZ125 MTZ144 MTZ160 836 5 1500 870 LBP application 50 Hz Compressor H W D OP LCQN048 NTZ048 545 630 650 OP LCQN068 NTZ068 705 900 900 OP LCQN096 OP LCQN108 OP LCQN136 NTZ096 NTZ108 NTZ136 836 5 1200 800 OP LGQN096 OP LGQN108 OP ...

Page 2: ...0 Evaporating Temperature C R407C Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R452A Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R407F Ambient Temperature C 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 20 Evaporating Temperature C R134a Ambient Temperature C SH 10 K SC 0 K MBP Fig 1a 45 0 10 20 30 4...

Page 3: ...Instructions Danfoss DCS CC 2018 07 3 FRCC PI 059 A1 02 1 x coil height Min clearance 2 x unit length Fig 2 Fig 3 Fig 4 ...

Page 4: ...Instructions 4 Danfoss DCS CC 2018 07 FRCC PI 059 A1 02 SINGLE PHASE MODELS THREE PHASE MODELS ...

Page 5: ...Instructions Danfoss DCS CC 2018 07 5 FRCC PI 059 A1 02 For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar ...

Page 6: ... stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety measures prior to assembly All installation and servicing is to be performed by qualified personnel in compliance with all pertinent practices and safety procedures The condensing unit must be located in...

Page 7: ...tent with system volume Never use the compressor as a vacuum pump It is recommended to use large diameter connec tion lines and to connect these lines to the shut off valves rather than to the Schrader connec tion This recommendation allows avoiding excessive pressure losses Moisture level At the time of commissioning system moisture content may be as high as 100 ppm During ope ration the liquid l...

Page 8: ...s fan opera tions water flow water filter etc liquid refrige rant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge the correct refrige rant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrigerant pressure tables pressure tempe rature the superheat and the sub cooling etc if additional...

Page 9: ...User advisory Insist that all service operations only be per formed by qualified personnel The condensing unit tubing and compressor surface temperatures may exceed 100 C 212 F and cause severe bodily burns Special precau tion must be taken when working around the compressor and refrigerant tubing Moreover a compressor in operation can generate very cold surface temperatures as low as 45 C 49 F th...

Reviews: