NovoCon® S  CO6, Energy, I/O - High Accuracy Actuator

E100 VXX
281624
0030471

E100 VXX
281624
0030471

MADE IN SLOVENIA

NovoCon

 

  S CO6, Energy, I/O

003Z8503

Actuator for AB-QM DN10-32

Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA

®

6430 Nordborg, Denmark

Power: 24VAC/DC, 50/60 HZ

Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm

Consumption: 3.9VA running. Standby 0.9W

IP54/40, -10T55

III

01

E100 VXX
281624
0030471

E100 VXX
281624
0030471

MADE IN SLOVENIA

NovoCon

 

  S CO6, Energy, I/O

003Z8503

Actuator for AB-QM DN10-32

Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA

®

6430 Nordborg, Denmark

Power: 24VAC/DC, 50/60 HZ

Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm

Consumption: 3.9VA running. Standby 0.9W

IP54/40, -10T55

III

01

01

Serial number can be removed from the 
NovoCon® S and added to installation drawing.

Device Object 
Instance Number

NovoCon® S

CO6, Energy, I/O

Application mode:

MSV:9 / 32810

Digital control (default), 

Analog control, 

CO6 mode, 

Inverted CO6 mode

Select Valve Type

MSV:3 / 32802

(default AB-QM DN 15)

Design Flow Rate

in Digital / Analog mode

AV:0 / 32768

in CO6 mode 

AV:30 / 32796 Heating 

AV:31 / 32798 Cooling

Presettings

DIP Switch

DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment 
method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU.
For termination of last unit on the field bus, turn DIP Switch 8 ON.
Dip switch 9 is not used.
Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON).
When the protocol is changed on DIP Switch 10, a power cycle is required.

1

2

3

4

5

6

7

8

9

10

ON

OFF

 To avoid injury and damage to persons and 

devices, it is absolutely necessary these 

instructions are carefully read and observed 

prior to assembly and commissioning.

Necessary assembly, start-up, and maintenance work 

must be performed only by qualified, trained and 

authorised personnel.

Switch off the power line before wiring the actuator.

 

Connect via safety isolating transformer.

Galvanic separations shall be provided for 
segments crossing buildings.

 

Always follow the local disposal regulations.

Safety Note

Safety Note

Safety Note

If the NovoCon® S network is supplied with 

two or more AC power boosters, caution must 

be observed when disconnecting one of the 

transformers from the high voltage power 

line. As the NovoCons are connected in a daisy chain, 

there may be high voltage on the primary side of the 

disconnected power supply. Disconnect always both 

the primary and secondary side of the transformer.

Safety Note