background image

© Danfoss | 2017.05

VI.HU.I3.02 | 1

NovoCon® S  CO6, Energy, I/O 

- High Accuracy Actuator

Operating Guide

IP40

IP54

IP5

4

IP5

4

Calibration:
Press button 

 until two 

LED’s are turned on
DIP switch: 

Manual override:
Adjust wheel 

NovoCon® analog cable

*VIHUI302*

Common ground shall be 
used for all devices on the 
same network.

Digital port

Port for CO6 actuator or Energy cable, I/O cable, 
analog cable or voltage booster.

Digital port

Actuator NovoCon® ChangeOver

6

 Flexible

NovoCon® Energy cable

- PT1000 surface sensors

NovoCon® Energy cable

- PT1000 immersed sensors

NovoCon®  I/O cable

Red 

Power 24V

Black GND

Grey 

Analog input

Blue 

Analog input ground

NovoCon® digital cable

Red Power

Black 

Green 

´+´ non-inverting signal wire

White/green  ´−´ inverting signal wire

Common ground for power 
and bus signal wire

Purple O-ring

Actuator NovoCon® 

ChangeOver

6

Red 

Power 24V

Black GND

White 

CO6 Control signal 

Grey 

CO6 Feedback signal

Blue O-ring

Actuator NovoCon® 

ChangeOver

6

 Energy

Red 

Power 24V

Black 

Power ground. T1, T2 and V output signal ground.

Blue 

V/mA input signal ground

Grey 

V/mA input signal

White 

V output signal

Yellow 

T1 or resistance input

Orange   T2 or  resistance input