background image

FRCC.PI.036.A2.02

1- 8510278P01B 

© Danfoss | DCS (CC) | 2016.04

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products 

already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S, 6430 Nordborg, Denmark

1 – Introduction

These instructions pertain to the Danfoss scroll 

compressors  MLZ/MLM116 scroll compressors 

used for refrigeration systems. They provide 

necessary information regarding safety and 

proper usage of this product.

2 – Handling and storage

 •  Handle the compressor with care. Use the 

dedicated handles in the packaging. Use the 

compressor lifting lug and use appropriate and 

safe lifting equipment.

 • 

 

Store and transport the compressor in an 

upright position.

  •  Store the compressor between -35°C and 50°C.

 

• 

 

Don’t expose the compressor and the 

packaging to rain or corrosive atmosphere.

3 – Safety measures before assembly

 Never use the compressor in a flammable 

atmosphere.

 •  The compressor ambient temperature may not 

exceed 50°C during off-cycle.

 •  Mount the compressor on a horizontal flat 

surface with less than 3° slope.

  •  Verify that the power supply corresponds to 

the compressor motor characteristics (see 

nameplate).

 •  When installing MLZ/MLM116, use equipment 

specifically reserved for HFC refrigerants which 

was never used for CFC or HCFC refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 •  The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

4 – Assembly

 • 

 

In parallel assemblies of MLZ/MLM116 the 

compressor requires a rigid mounting on the 

rails. Use the rigid spacers from mounting kit 

777045 to connect compressor to rails. For rail 

and frame connection, use rubber grommet from 

manifolding kit (7777041 for tandem and quadro 

/ 7777049 for trio). Never use rigid connection 

between rail and frame.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Remove the gaskets when brazing rotolock 

connectors.

 •  Always use new gaskets for assembly.

 •  Connect the compressor to the system as soon 

as possible to avoid oil contamination from 

ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 • 

 

Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas flow.

 • 

 

Connect the required safety and control 

devices. When the schrader port is used for 

this, remove the internal valve.

 • 

 

Do not exceed the maximum tightening 

torque for rotolock connections: 

Rotolock connections

Tightening torque

1 3/4” rotolock

110 Nm

2 1/4” rotolock

130 Nm.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

  •  Pressurize the system on HP side first and then on 

LP side. Never let the pressure on LP side exceed 

the pressure on HP side with more than 5 bar. 

Such pressure difference could cause internal 

compressor damage.

 •  Do not use dye for leak detection.

  •  Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed : 

Models

LP side

HP side

MLZ/MLM116

25 bar

32 bar

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

  •  Never use the compressor to evacuate the system.

  •  Connect a vacuum pump to both the LP & HP sides.

 •  Pull down the system under a vacuum of 

500µm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply. 

See overleaf for wiring details.

 •  All electrical components must be selected as per 

local standards and compressor requirements.

 •  Refer to page  2 for electrical connections details.

 

• 

 

The Danfoss scroll compressors  scroll 

compressor only works correctly in one 

rotation direction. Line phases L1, L2, L3 

must absolutely be connected to compressor 

terminals T1, T2, T3 to avoid reverse rotation.

 •   Please make sure M1/M2 is connected to OEM 

controller and L/N is connected to ouside 

power supply, otherwise, there will be no 

motor protection.

 •  Use ø 4.8 mm (3/16”) screws and ¼” ring 

terminals for the power connection. Fasten 

with 3 Nm torque.

 •  The thermostat connection (if present) is a ¼” 

AMP-AWE spade connector.

 •  The compressor must be connected to earth 

with the 5 mm earth terminal screw.

8 – Filling the system

 •  Keep the compressor switched off.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. The charge must 

be as close as possible to the nominal system 

charge to avoid low pressure operation and 

excessive superheat. Never let the pressure 

on LP side exceed the pressure on HP side 

with more than 5 bar. Such pressure difference 

could cause internal compressor damage.

 

• 

 

Keep the refrigerant charge below the 

indicated charge limits if possible. Above this 

limit; protect the compressor against liquid 

flood-back with a pump-down cycle or suction 

line accumulator.

 •  Never leave the filling cylinder connected to 

the circuit.

Compressor models Refrigerant charge limit (kg)

MLZ/MLM116

13.5

 

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 

with both generally and locally applicable 

regulations and safety standards. Ensure that 

they are operational and properly set. 

 Check that the settings of high-pressure 

switches and relief valves don’t exceed the 

maximum service pressure of any system 

component.

 • 

 

A low-pressure switch is recommended to 

avoid vacuum operation. Minimum setting 

for MLM116: 0.5 bar g. Minimum setting for 

MLZ116 : 0.7 bar g.

 

• 

 

Verify that all electrical connections are 

properly fastened and in compliance with local 

regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shutdown for 

belt type crankcase heaters (6 hours for surface 

sump heaters).

10 – Start-up

 •  Never start the compressor when no refrigerant 

is charged.

  •  All service valves must be in the open position.

 •  Balance the HP/LP pressure.

 •  Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 

conformity and voltage on terminals.

 • 

 

Eventual reverse rotation can be detected 

by following phenomena; the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the 

compressor immediately and connect the 

phases to their proper terminals. MLZ/MLM116 

scroll compressors  scroll compressors are 

protected against reverse rotation  by the 

external electronic protection module. They 

will shut off automatically.  

11 – Check with running compressor

 •  Check current draw and voltage.

  •  Check suction superheat to reduce risk of slugging.

 •  Observe the oil level in the sight glass for about 60 

minutes to ensure proper oil return to the compressor.

 •  Respect the operating limits.

 

• 

 

 

Check all tubes for abnormal vibration. 

Movements in excess of 1.5 mm require 

corrective measures such as tube brackets.

 • 

 

When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as far 

as possible from the compressor. The compressor 

must be operating during this process.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor 

problems, following periodic maintenance is 

recommended:

 •   Verify that safety devices are operational and 

properly set.

 •   Ensure that the system is leak tight.

 •   Check the compressor current draw.

 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •   Check that all electrical connections are still 

adequately fastened.

 • 

 

 

Keep the compressor clean and verify the 

absence of rust and oxidation on the compressor 

shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial 

number with any claim filed regarding this product.

The product warranty may be void in following 

cases:

  •   Absence  of  nameplate.

 •   External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •   Compressor opened or returned unsealed.

 •   Rust, water or leak detection dye inside the 

compressor.

 •   Use of a refrigerant or lubricant not approved 

by Danfoss.

 •   Any deviation from recommended instructions 

pertaining to installation, application or 

maintenance.

  •   Use  in  mobile  applications.

 •   Use in explosive atmospheric environment.

 •   No model number or serial number transmitted 

with the warranty claim.

 14 – Disposal

Danfoss recommends that compressors 

and compressor oil should be recycled 

by a suitable company at its site.

L N S1 S2 M1 M2

L1 L2 L3

Black  Blue  Brown

 

 

Phase sequence input

Internal control contact

Safety

circuit

Thermistor

connection

Module power

L N

M1 M2

Reviews: