Service guide | Application, Installation and Maintenance Manual MCHE

 

5

AX292455807588en-000101 | 01.2019 |

Consider the following during bending:

• 

MCHEs are constructed of soft aluminum 

and are susceptible to deformation during 

handling . Prior to bending operation, make 

sure the MCHE is flat, square and undam-

aged . Consider a sizing operation to ensure 

this .

• 

Make sure the coils are loaded into the 

bender in a way that keeps them flat square 

and undamaged . 

• 

Keep the flat tubes perpendicular to the 

spindle while bending the coil .

• 

Clamp the coil during the bending process, 

being careful not to crush it . 

• 

Slower bending speeds will often yield 

better results .

• 

Vertical spindle bending machines are often 

set up so that the microchannel coil ends up 

sliding along the table with all its weight 

supported by the header ends and/or the 

bottom dead tube . 

 

During the bending operation, do not let   

 

one end of the coil become cantilevered off  

 

the edge the table, because this can cause  

 

the coil to droop with the tubes being  

 

 

non-perpendicular to the spindle, resulting  

 

in corkscrewing or reduced bend quality    

 

and/or consistency .  Note that with some    

 

benders, a portion of the supporting table  

 

will drop down during bending, creating    

 

opportunities for cantilever loads and  

 

 

improper bending .

• 

 Bending multi-bend coils on a horizontal     

 spindle bender can cause cantilevered      

 loads resulting from the dead weight of the  

 unsupported bent legs .  As an example, a    

 coil with three (3) bends, depending on     

 fixturing, may result in the load of the first    

 75% of the coil being transferred into the     

 remaining coil leg, possibly causing poor     

 bend quality and/or permanent deforma   

 tion .  Bending challenges are greater with   

 MCHE’s than similar fin and tube coils,  

 

 requiring proper fixturing .

3. Installation

3.1  Pass arrangement 

Carefully identify the locations of the inlet and 

outlet tubes . Microchannel condensers is often 

designed with multiple passages (parallel flow) 

that have fewer tubes in each successive pass 

(Fig . 2)

Danfoss MCHEs include a small notch in both 

headers to indicate that this is the bottom of the 

heat exchanger .  Additionally, a product label is 

placed on the outermost tube (unless specified 

elsewhere by the customer), indicating the top of 

the heat exchanger .

Incorrectly connecting the inlet and outlet tubes 

of a MCHE will likely result in excessive refrige-

rant side pressure drop and poor heat transfer .

Fig . 2 MCHE passes distribution

3.2  Fan location and size

Air distribution may have an influence on the 

performance of the MCHE . For good air distribu-

tion choosing a fan with proper fan diameter and 

keeping a constant distance between the coil 

and the fan is desirable . We recommend 

selecting a fan diameter that is as close as 

possible to the smallest of MCHE height and 

length . The distance between MCHE and fan is

)

recommended to be at least 15 times the width/

depth of MCHE coil when possible (Fig .3) .

MCHE

Fan Installation Face

H

L

Disstance

Fig . 3 Fan location and size

Outlet

Few tubes

Inlet

Many tubes

2

3

4

Summary of Contents for MicroChannel Heat Exchanger

Page 1: ...ro solutions com User manual Installation Operation and Maintenance Manual APP pumps APP 21 43 Service guide MicroChannel Heat Exchangers MCHE Installation and Maintenance Guide www danfoss com ...

Page 2: ...age and working environments 5 2 1 Storage 5 2 2 Handling 5 2 3 Bending procedure 5 3 Installation 6 3 1 Pass arrangement 6 3 2 Fan location and size 6 3 3 Coil mounting against thermal expansion 7 3 4 Elimination of gaps 8 3 5 Prevention of galvanic corrosion 8 3 6 Vibration 9 4 Leak repair 9 5 Coating 10 6 Maintenance 10 6 1 Filters 10 6 2 Shut down periods 10 6 3 Cleaning procedure 10 ...

Page 3: ...o comply with the instructions in this manual and or due to incorrect installation operation and mainte nance of MCHEs All personnel being responsible for operation and maintenance of theeat exchanger unit must read and fully understand these instruc tions before Transportation of the MCHE unit Lifting the unit Installing the MCHE unit Servicing the MCHE unit Maintaining the MVHe unit 1 2 General ...

Page 4: ...d that MCHEs be shipped flat and formed at the customer s location Bending Radius The minimum bend radius required to achieve acceptable manufacturing yields is a function of the microchannel tube fin and alloy the overall capabilities of the bending equipment including fixturing bending speed and bending length NOTE Conducting trial bending runs of the specific coil and configuration are recommen...

Page 5: ...upported bent legs As an example a coil with three 3 bends depending on fixturing may result in the load of the first 75 of the coil being transferred into the remaining coil leg possibly causing poor bend quality and or permanent deforma tion Bending challenges are greater with MCHE s than similar fin and tube coils requiring proper fixturing 3 Installation 3 1 Pass arrangement Carefully identify...

Page 6: ...f movement Mounting methods as indicated in Figures 5a and 5b are recommended Steel frame Sealing Sealing MCHE Fig 5a Mounting by bracket Fig 5b Mounting by end plate Inlet outlet connections are not designed to be used as handles support mating tubes resist thermal expansion or be forced into position with mating tubes during assembly etc In particular Inlet outlet connections must be assembled s...

Page 7: ...heat shield may be required to protect the MCHE s tubes and fins from the brazing torch The recommended pipe length L after the brazing joint should be greater than or equal to 70mm as shown in the picture below Fig 7 L 70 mm Fig 7 Recommended length of inlet outlet connections 3 4 Elimination of gaps To maximize heat transfer performance gaps should be eliminated on both sides of the face of the ...

Page 8: ...s in the case to prevent the MCHE from the influence of vibration is using rubber washers on the brackets or rubber supports on the manifolds fig 10a 10b Name Parameter Amplitude mm 0 15 peak to peak is 0 3 mm Acceleration m s 2 20 Table 2 The allowable vibration ranges Inlet Outlet 10 mm 10 mm Fig 9 Recommend test points of vibration Fig 10a Rubber washer Fig 10b Rubber support 4 Leak repair is n...

Page 9: ...ods During periods when the MCHE is not operated for longer than a week the MCHE must be completely cleaned following the cleaning procedure This practice must also be performed during short shut down periods where corrosive deposits accumulate on the MCHE 6 3 Cleaning procedure Relative to tube fin heat exchangers Micro Channel heat exchanger coils tend to accumu late more dirt on the surface of ...

Page 10: ... Danfoss DCS im 2019 01 AX292455807588en 000101 10 Danfoss MicroChannel Heat Exchangers Jia Xing Co Ltd No 8 Sangdelan Road Wuyuan Street Haiyan Zhejiang Province 314300 P R China www danfoss com ...

Reviews: