Installation Guide

Electronic controller

MCX08M2 

with TTL

080R9348

AN358818754869en-000201

© Danfoss | DCS (vt) | 2021.01

AN358818754869en-000201 | 1

General features:

MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers 
in the compact size of 8 DIN modules: programmability, connection to the CANbus local 
network, Modbus RS485 serial communication interface. 
MCX08M2 with TTL version is moreover available in the version with display and power supply 
110 – 230 V AC.

MCX08M2 with TTL

ANALOG INPUTS

NTC, 0/1 V, 0/5 V, 0/10 V, PT1000, selectable via software

4

Universal NTC, Pt1000, 0/1 V, 0/5 V, 0/10 V, ON/OFF, 0/20 mA, 4/20 mA, selectable via software

4

Total number

8

DIGITAL INPUTS

Voltage free contact

8

Total number

8

ANALOG OUTPUTS

0/10 V DC optoinsulated

2

0/10 V DC, PWM, PPM selectable via software

2

Total number

4

DIGITAL OUTPUTS

SPST relay 16 A (normally open contacts)

2

SPST relay 8 A (normally open contacts)

2

SPDT relay 8 A (changeover contacts)

4

Total number

8

OTHERS

Power supply 110 V / 230 V AC

Connection for programming key

Connection for remote display and keyboard

Buzzer

CANbus

RTC clock

Modbus RS485 serial interface

Serial TTL

Dimensions (DIN modules)

8

Mounting

DIN rail

Summary of Contents for MCX08M2

Page 1: ...2 with TTL ANALOG INPUTS NTC 0 1 V 0 5 V 0 10 V PT1000 selectable via software 4 Universal NTC Pt1000 0 1 V 0 5 V 0 10 V ON OFF 0 20 mA 4 20 mA selectable via software 4 Total number 8 DIGITAL INPUTS Voltage free contact 8 Total number 8 ANALOG OUTPUTS 0 10 V DC optoinsulated 2 0 10 V DC PWM PPM selectable via software 2 Total number 4 DIGITAL OUTPUTS SPST relay 16 A normally open contacts 2 SPST ...

Page 2: ...ust be performed by qualified personnel The device can t be used as a safety device Liability for injury or damage caused by the incorrect use of the device lies solely with the user Installation warnings Mounting position recommended vertical The installation must be executed according the local standards and legislation of the country Always operate on the electrical connections with the device ...

Page 3: ...C optoins 2 AO3 AO4 Analog outputs optoinsulated 0 10 V DC minimum load 1K Ω 10 mA for each output PWM PPM 0 10VDC 2 AO1 AO2 Analog outputs selectable via software between 0 10 V dc minimum load 1K Ω 10 mA for each output pulsing output synchronous with the line at modulation of impulse position PPM or modulation of impulse width PWM pulsing output at modulation of impulse position PPM with range ...

Page 4: ...CX08M2 TOP PWM PPM 0 10 Vdc 0 10 V optoinsulated NTC 0 1 V 0 5 V 0 10 V PT1000 To the AI 100 mA max To the AI 120 mA max Not used RX TX DIR 5V AUX COM TTL only for 080G0335 MCX08M2 TOP MCX08M2 BOTTOM NTC 0 1 V 0 5 V 0 10 V PT1000 AI max To the AI 120 mA max Danfoss 80G8036 04 DIR 5V AUX 0G0335 ...

Page 5: ... plug in connector type pitch 5 mm section cable 0 2 2 5 mm Digital input 1 8 connector 10 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm Analog input 5 8 connector 5 way screw plug in connector type pitch 5 mm section cable 0 2 2 5 mm TTL connector only for 080G0335 5 way spring plug in connector type pitch 2 5 mm section cable 0 2 2 5 mm Bottom Board Power supply connector ...

Page 6: ...s DCS vt 2021 01 6 AN358818754869en 000201 Product part numbers Accessories part numbers Description Code No MCX08M CONNECTORS KIT 080G0180 Description Code No MCX08M2 230 V LCD RS485 TTL Single Pack 080G0335 ...

Reviews: