8510223 P01-A © Danfoss Commercial Compressors March 2006
Instructions
• Connection to mains and earthing:
Mains and earthing connections
3 Phase
Power
Input
91 (L1)
92 (L2)
93 (L3)
95 PE
• Motor connections
• Control cables
Control cables must be screened/armoured. Use
the clamp from the accessory bag to connect
the screen to the decoupling plate for control
cables.
Motor cable must be screened/armoured. Use
the accessory decoupling plate. Make sure the
earth wire is connected to the earth terminal
on this plate and install the screened part of the
motor cable as shown on the above drawings.
Earth wire and screen cable part must be earth
connected on both end of the cable: frequency
converter and compressor.
Fig 9