SYSTEM DESIGN RECOMMENDATIONS

Models
NTZ048 - NTZ068 - NTZ096 - 
NTZ108 - NTZ136

Models
NTZ215 - NTZ271

Liquid line solenoid valve & 
pump-down

In refrigeration applications, the Liq-
uid Line Solenoid Valve (LLSV) is highly 
recommended. During the off -cycle, 
the LLSV isolates the liquid charge in 
the condensor side, thus preventing 
refrigerant transfer or excessive migra-
tion of refrigerant into the compres-
sor. Furthermore, when using LLSV in 

conjunction with the pump-down cy-
cle (especially in low-temperature ap-
plications), the quantity of refrigerant 
in the low-pressure side of the system 
will be reduced.
A pump-down cycle design is required 
when evaporators are fi tted with elec-
tric defrost heaters.

Suction accumulator

A suction accumulator off ers  consid-
erable protection against refrigerant 
fl oodback both at start-up and dur-
ing operation or after the defrost op-
eration. This device also helps protect 
against off -cycle migration by provid-
ing additional internal free volume to 
the low pressure side of the system.
The suction accumulator must be se-

lected in accordance with the accumu-
lator manufacturer recommendations. 
As a general rule, Danfoss Commercial 
Compressors recommends to size the 
accumulator for at least 50% of the to-
tal system charge. Tests however must 
be conducted to determine the opti-
mal size.

Crankcase heater

A crankcase heater protects against 
the off -cycle migration of refrigerant 
and proves eff ective if oil temperature 
is maintained 10 K above the saturat-
ed LP temperature of the refrigerant. 
Tests must thereby be conducted to 
ensure that the appropriate oil tem-
perature is maintained under all ambi-
ent conditions. A PTC crankcase heater 
is required with all Maneurop®‚ NTZ 
compressors. PTC crankcase heaters 
are self-regulating.

Under extreme conditions such as low 
ambient temperature at –15°C or low-
er a belt type crankcase heater could 
be used in addition to the PTC heater, 
although this is not a preferred solu-
tion for 1 and 2 cylinder compressors. 
The belt crankcase heater must be 
positioned on the compressor shell as 
close as possible to the oil sump to en-
sure good heat transfer to the oil. The 
below illustrated mounting positions 
are recommended:
Belt crankcase heaters are not self-
regulating. Control must be applied to 
energise the belt heater once the com-
pressor has been stopped and then to 
de-energise it while the compressor is 
running. The belt heater must be en-
ergised 12 hours before restarting the 
compressor following an extended 
down period.
If the crankcase heater is not able to 
maintain the oil temperature at 10 K 
above the saturated LP temperature 
of the refrigerant during off  cycles or 
if repetitive fl oodback is present a the 
Liquid Line Solenoid Valve (LLSV) + 
pump-down cycle is required, possibly 
in conjunction with a suction accumu-
lator.

Summary of Contents for Maneurop NTZ Series

Page 1: ...MAKING MODERN LIVING POSSIBLE SELECTION APPLICATION GUIDELINES Maneurop reciprocating compressors NTZ R404A R507A...

Page 2: ......

Page 3: ...and relays 11 Single phase motor protection and suggested wiring diagram 11 Three phase electrical characteristics 13 Three phase motor protection and suggested wiring diagram 13 REFRIGERANTS AND LUB...

Page 4: ...TZ range The NTZ series is engineered as a true low temperature compressor opti mised at 35 C with an extended evaporating temperature range from 45 C up to 10 C The compressors can be operated at a r...

Page 5: ...5 120F0171 NTZ215 120F0031 120F0006 120F0172 NTZ271 120F0032 120F0007 120F0173 NTZ430 120F0024 NTZ542 120F0025 Compressor model Code no Motor voltage code 1 3 4 5 9 Nominal voltage 208 230 1 60 200 23...

Page 6: ...nominal ratings Operating envelope R404A R507A Motor code 4 operating conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to Online Datas...

Page 7: ...ck 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8 40 23 15 Silent block 7 1 cylinder OUTLINE DRAWINGS Rotolock connections size Pipe sizing...

Page 8: ...1 8 38 82 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 HM8 40 23 15 Silent block 8 OUTLINE DRAWINGS 2 cylinders Rotolock connections size Pipe sizing Rotolock valve S...

Page 9: ...ting hole for PTC crankcase heater Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 VE version only Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction D...

Page 10: ...ng 54 with cable gland Screw 10 32 UNF x 9 5 Earth M4 12 Knock out 29 mm 29 mm Models NTZ048 NTZ068 NTZ096 NTZ108 NTZ136 except NTZ136 1 Spade connectors 1 4 AMP AWE Earth M4 12 Knock out 21 mm 21 mm...

Page 11: ...internally protected by a temperature current sensing bimetallic protector which senses the main and start wind ing current as well as motor winding temperature If the motor were to be overloaded and...

Page 12: ...capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main Capac...

Page 13: ...t out It might take up to several hours to reset and restart the compressor FU Fuses MS Main switch C1 Compressor contactor TH Thermostat EC External controls COMP Compressor PTC Crankcase heater IOL...

Page 14: ...th pump down cycle Control device TH Optional short cycle timer 3 min 5 pts 180 s Control relay KA Liquid Solenoid valve LLSV Compressor contactor KM Safety lock out relay KS Pump down control L P swi...

Page 15: ...ase For most other aspects howev er this small glide may be neglected R507Aisanazeotropicmixturewithout temperature glide R407A and R407B have different thermodynamic properties than R404A and R507A E...

Page 16: ...t of oil circulating through the system is small it will contribute to good system operation and improved heat transfer efficiency Lubricant getting trapped in the evaporator or suction lines will aff...

Page 17: ...eparator is recom mended Also refer to the section Oil charge and oil level Filter driers For new installations with NTZ com pressors Danfoss recommends using the Danfoss DML 100 molecular sieve solid...

Page 18: ...ondensor may be installed indoor When the compressor is located in a low ambient temperature environ ment increased refrigerant migration will occur during shut down periods For such conditions an ext...

Page 19: ...ute runtime after each start and a 3 minute idle time between each stop and start Only during the pump down cycle may the compressor run for much shorter intervals Vavg Mean voltage of phases 1 2 and...

Page 20: ...re frigerant charge can condensate in the compressor crankcase A large amount will dissolve in the compressor oil un til the oil is completely saturated with refrigerant When the compressor is started...

Page 21: ...pti mal size Crankcase heater A crankcase heater protects against the off cycle migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturat ed LP temperature...

Page 22: ...next section Sound Compressors in operation are one of the sources of sound and vibration in a refrigeration system Both phenom ena are closely related Vibration The mounting grommets delivered with...

Page 23: ...s and using tools chargingsystems tubes vacuum pumps etc dedicated for R404A and R507A Compressor handling mounting and connection Component Torque Nm Min Max Rotolock suction valve NTZ048 NTZ068 80 1...

Page 24: ...rge can escape via the discharge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated...

Page 25: ...capacity appropriate for the sys tem volume It is recommended to use connection lines with a large diameter and to connect these lines to the serv ice valves and not to the schrader con nection so as...

Page 26: ...noted while the expansion valve setting is correct the suction line insulation between evaporator and compressor should be checked and eventually replaced by a higher qual ity insulation z A too high...

Page 27: ......

Page 28: ...reduce costs streamline processes and achieve your business goals Danfoss A S www danfoss com FRCC PC 002 A2 02 Replace FRCC PC 002 A1 02 May 2005 Produced by Danfoss CC DSS 02 2007 The Danfoss produc...

Reviews: