SYSTEM DESIGN RECOMMENDATIONS

Operating limits

NTZ – R404A / R507A

Working pressure range, high side

 

(bar gauge)

13.2 – 27.7

Working pressure range, low side

 

(bar gauge)

0.1 – 3.3

Minimum low pressure safety 
switch setting

 

(bar gauge)

0

Minimum low pressure pump-down 
switch setting

 

(bar gauge)

0.1

Relief valve opening pressure diff erence

 

(bar)

30

Relief valve closing pressure diff erence

 

(bar)

8

Low ambient temperature 
operation

At low ambient temperatures, the con-
densing temperature and condensing 
pressure in air cooled condensors will 
decrease. This low pressure may be 
insuffi

  cient to supply enough liquid 

refrigerant to the evaporator. As a re-
sult the evaporating temperature will 
decrease, leading to low capacity and 
eventual poor oil return. At start-up, 
the compressor will pull into vacuum 
and it will be switched off  by the low 
pressure protection. Depending on 
how the low pressure switch and delay 
timer are set, short cycling can occur. 
To avoid these problems, several solu-
tions are possible, based on reducing 
condenser capacity:

z

  Liquid fl ooding of condensors (note: 

this solution requires extra refrig-

erant charge. A non-return valve 
in the discharge line is required 
and special care should be taken 
when designing the discharge line.)

z

 Reduce air fl ow to condensors

z

  Alternatively the condensor may be 

installed indoor.

When the compressor is located in a 
low ambient temperature environ-
ment, increased refrigerant migration 
will occur during shut down periods. 
For such conditions an extra belt-type 
crankcase heater is strongly recom-
mended.
Note that with 100% suction gas 
cooled motors, Maneurop® compres-
sors can be externally insulated. Refer 
to section "Liquid refrigerant migra-
tion & charge limits" for more details.

Low pressure

A low-pressure (LP) safety switch 
must also be used; deep vacuum op-
erations will result in failure. The mini-
mum LP safety switch (loss of charge 
switch) setting is 0 relative bar (0 bar 
g). For systems without pump-down 
feature, the LP safety switch must be 
either a manual lockout device or an 

automatic LP safety switch wired into 
an electrical lockout circuit. LP switch 
tolerance must not allow for vacuum 
operation of the compressor. LP safety 
switch settings for pump-down cycles 
with automatic reset are listed in the 
following table.

High pressure

A high-pressure (HP) safety switch is 
required to shut down the compressor 
should the discharge pressure exceed 
the values shown in the table below. 
This switch can be set at lower values 
depending on the application and 
ambient conditions. It must be either 
located in a lockout circuit or associ-

ated with a manual reset device to 
prevent cycling around the high pres-
sure limit.
If a discharge valve is used, the HP 
switch must be connected to the serv-
ice valve gauge port, which cannot be 
isolated.

Summary of Contents for Maneurop NTZ Series

Page 1: ...MAKING MODERN LIVING POSSIBLE SELECTION APPLICATION GUIDELINES Maneurop reciprocating compressors NTZ R404A R507A...

Page 2: ......

Page 3: ...and relays 11 Single phase motor protection and suggested wiring diagram 11 Three phase electrical characteristics 13 Three phase motor protection and suggested wiring diagram 13 REFRIGERANTS AND LUB...

Page 4: ...TZ range The NTZ series is engineered as a true low temperature compressor opti mised at 35 C with an extended evaporating temperature range from 45 C up to 10 C The compressors can be operated at a r...

Page 5: ...5 120F0171 NTZ215 120F0031 120F0006 120F0172 NTZ271 120F0032 120F0007 120F0173 NTZ430 120F0024 NTZ542 120F0025 Compressor model Code no Motor voltage code 1 3 4 5 9 Nominal voltage 208 230 1 60 200 23...

Page 6: ...nominal ratings Operating envelope R404A R507A Motor code 4 operating conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to Online Datas...

Page 7: ...ck 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8 40 23 15 Silent block 7 1 cylinder OUTLINE DRAWINGS Rotolock connections size Pipe sizing...

Page 8: ...1 8 38 82 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 HM8 40 23 15 Silent block 8 OUTLINE DRAWINGS 2 cylinders Rotolock connections size Pipe sizing Rotolock valve S...

Page 9: ...ting hole for PTC crankcase heater Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 VE version only Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction D...

Page 10: ...ng 54 with cable gland Screw 10 32 UNF x 9 5 Earth M4 12 Knock out 29 mm 29 mm Models NTZ048 NTZ068 NTZ096 NTZ108 NTZ136 except NTZ136 1 Spade connectors 1 4 AMP AWE Earth M4 12 Knock out 21 mm 21 mm...

Page 11: ...internally protected by a temperature current sensing bimetallic protector which senses the main and start wind ing current as well as motor winding temperature If the motor were to be overloaded and...

Page 12: ...capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main Capac...

Page 13: ...t out It might take up to several hours to reset and restart the compressor FU Fuses MS Main switch C1 Compressor contactor TH Thermostat EC External controls COMP Compressor PTC Crankcase heater IOL...

Page 14: ...th pump down cycle Control device TH Optional short cycle timer 3 min 5 pts 180 s Control relay KA Liquid Solenoid valve LLSV Compressor contactor KM Safety lock out relay KS Pump down control L P swi...

Page 15: ...ase For most other aspects howev er this small glide may be neglected R507Aisanazeotropicmixturewithout temperature glide R407A and R407B have different thermodynamic properties than R404A and R507A E...

Page 16: ...t of oil circulating through the system is small it will contribute to good system operation and improved heat transfer efficiency Lubricant getting trapped in the evaporator or suction lines will aff...

Page 17: ...eparator is recom mended Also refer to the section Oil charge and oil level Filter driers For new installations with NTZ com pressors Danfoss recommends using the Danfoss DML 100 molecular sieve solid...

Page 18: ...ondensor may be installed indoor When the compressor is located in a low ambient temperature environ ment increased refrigerant migration will occur during shut down periods For such conditions an ext...

Page 19: ...ute runtime after each start and a 3 minute idle time between each stop and start Only during the pump down cycle may the compressor run for much shorter intervals Vavg Mean voltage of phases 1 2 and...

Page 20: ...re frigerant charge can condensate in the compressor crankcase A large amount will dissolve in the compressor oil un til the oil is completely saturated with refrigerant When the compressor is started...

Page 21: ...pti mal size Crankcase heater A crankcase heater protects against the off cycle migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturat ed LP temperature...

Page 22: ...next section Sound Compressors in operation are one of the sources of sound and vibration in a refrigeration system Both phenom ena are closely related Vibration The mounting grommets delivered with...

Page 23: ...s and using tools chargingsystems tubes vacuum pumps etc dedicated for R404A and R507A Compressor handling mounting and connection Component Torque Nm Min Max Rotolock suction valve NTZ048 NTZ068 80 1...

Page 24: ...rge can escape via the discharge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated...

Page 25: ...capacity appropriate for the sys tem volume It is recommended to use connection lines with a large diameter and to connect these lines to the serv ice valves and not to the schrader con nection so as...

Page 26: ...noted while the expansion valve setting is correct the suction line insulation between evaporator and compressor should be checked and eventually replaced by a higher qual ity insulation z A too high...

Page 27: ......

Page 28: ...reduce costs streamline processes and achieve your business goals Danfoss A S www danfoss com FRCC PC 002 A2 02 Replace FRCC PC 002 A1 02 May 2005 Produced by Danfoss CC DSS 02 2007 The Danfoss produc...

Reviews: