background image

© Danfoss | DCS (ms) | 2020.05

4 | AN317523977313en-000201

Red light LED

Yellow light LED

Green light LED

Fig. 9

Level

Open at no 

Liquid 

(Normally 

Open)*

Closed at no 

Liquid 

(Normally 

Closed)*

Voltage 

connected

Level detection LLS 4000/4000U 

Fault

Green LED

Yellow LED

Red LED

High Level

sensor

High Level

sensor

Low Level

sensor

Low Level

sensor

Voltage supply 

outside 

spec. 

LLS 4000/4000U 

fault

**

***

Green LED ON

Yellow LED ON

Red LED ON

Green LED Flashing. 

LLS 4000/4000U 

connected to 

Bluetooth device  

* Configuration dependent. Non-SIL2 fully configurable. SIL2 fixed configuration and only applicable for High Level sensor 

**  For failure types please connect the device to the Bluetooth App, enter fault state mode, and read the failure type

*** Fault can be detected at any detected level, ie. 2 or all 3 lights on

SIL2 fixed 

configuration

Not recommended in these applications because

1)

 A High Level Alarm may not be registered at a power failure

2)

 A Low Level Alarm may not be registered at a power failure 

1)

2)

Summary of Contents for LLS 4000

Page 1: ...G QDV 15 BSV BSV BSV ICF 25 6 5A EKE 347 AKS 4100 LLG BSV GD SVA SNV SNV SVA SVA LLG SNV SVA SFA DSV SVA LLS 4000 SVA SVA SCA X RT 260A RT 260A SNV SNV SVA SVA SNV SNV SNV SVA SCA X FIA FIA LLS 4000 F...

Page 2: ...b ft pre tightening 45 degrees clockwise rotation 32 mm LLS 4000U Alu gasket Clean joining surfaces Weld connector Clean for particles LLS 4000U Weld connector NPT Note Horizontal installation Recomme...

Page 3: ...4 V DC 25 Hand tighten clockwise 2 3 1 1 Fig 7 Cable with M12 female connector Red Green White Black 1 2 3 4 Color code M12 cable Danfoss M12 cables 034G7073 M12 cable female x 2 meter 034G7074 M12 ca...

Page 4: ...ON Yellow LED ON Red LED ON Green LED Flashing LLS 4000 4000U connected to Bluetooth device Configuration dependent Non SIL2 fully configurable SIL2 fixed configuration and only applicable for High Le...

Page 5: ...supply may be needed Max cycles 1 000 000 Mechanical Data Max medium viscosity 5000 cps Max working pressure 65 bar 943 psi Ambient temperature range 40 C to 65 C 40 F to 149 F Medium temperature ran...

Page 6: ...Danfoss DCS ms 2020 05 6 AN317523977313en 000201 2 8 0 78 3 4 NPT H32 1 4 5 6 M12x1 0 77 0 6 Fig 10 M12x1 G3 4 36 H32 71 3 2 34 20 15 142 4 19 5 LLS 4000 mm LLS 4000U in...

Page 7: ...s DCS ms 2020 05 AN317523977313en 000201 7 Configuration LLS Bluetooth app download Pin code 0000 1 2 3 download Search Danfoss 4 LLS 4000 ABCDEFGHIJKL LLS______ 1 2 3 LLS_______ 4 5 6 Configurable LL...

Page 8: ...ion and operating conditions of the device respects those specified in this guide especially concerning the supply voltage and environmental conditions All service and maintenance operations must be p...