Adjustment spindles location

Note

Remove lockplate before thermostat

adjustment. Replace lockplate after

adjustment (if desired).

RANGE DIFFERENTIAL

See printed instruction on top of control 

See printed instruction on top of control

 

increase temp. (warmer): turn CW 

 

Increase: turn CW

 

decrease temp. (colder): turn CCW 

 

decrease: turn CCW

(use adjustment knob) 

(use adjustment knob or screwdriver)

Determination of differential

For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct differential.

Example:

HSP = 5.6 °C (45 °F) => 

DIFF (from graph):

LSP = 0 °C (32 °F)  

 

7.2 °C (13 °F) (value which has to be

 

 

set on diff. scale).

For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):

The differential will be HSP less LSP

Example: 

HSP  –   LSP  =  DIFF.

 

7 °C   –   5 °C  =  2 °C 

 

(45 °F)(35 °F) (10 °F)

Note:

(Load Option A)  

 

(Load Option B)

CUT-IN  =   HSP  or  CUT-IN  =   LSP

CUT-OUT =   LSP   

CUT-OUT  =   HSP