DKRCC.PI.CA0.C1.22 / 520H8304 

© Danfoss A/S (AC-MCI / jmn), 2013-11

Switch position

Contacts position

Aut.

Automatic control operation

µ Stop

1 and 2 are closed

1.  Adjust range spindle to desired 

1.  Adjust range spindle to desired

 

HIGH SET POINT (use hand knob) 

 

LOW SET POINT 

2.  Adjust differential spindle to 

2.  DIFFERENTIAL is fixed.

 

desired DIFFERENTIAL 

 

Value printed on scale plate

Setting

For KP 61, KP 62, KP 63, KP 68, KP 69, KP 71,                                                                                      KP 61 and KP 71 w/man. reset

KP 73, KP 75,  KP 77, KP 79 and KP 81 w/auto reset 

 

Note:

To find correct differential, see “Determination of differential”

HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT 

HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT  

Example: Example: 

HSP 

– 

DIFF. 

=  

LSP 

HSP 

– 

DIFF. 

LSP

7 °C 

– 

5 °C 

2 °C 

3 °C 

– 

3 °C 

0 °C

(45 °F) 

 

(10 °F) 

 

(35 °F) 

(37.4 °F) 

 

(5.4 °F) 

 

(32 °F)

KP w/ hand switch

 

CAUTION:

 

•  Hand switch breaks circuit by micro contact gab.

 

•  Use hand switch for service on refrigeration parts only

 

•  Cut out main switch before service on electrical parts

For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):

The differential will be HSP less LSP

Example: 

HSP  –   LSP  =  DIFF.

 

7 °C   –   5 °C  =  2 °C 

 

(45 °F)(35 °F) (10 °F)

Note:

(Load Option A)  

 

(Load Option B)

CUT-IN  =   HSP  or  CUT-IN  =   LSP

CUT-OUT =   LSP   

CUT-OUT  =   HSP

See “Wiring” 