12.2 Encoder Box Parameters
The following table shows the complete list of encoder box parameters found in the MPARAM.dat file. These parameters
can be adjusted.
There is always one parameter per line, consisting of the parameter group name followed by a dot and then the parameter
name. No spaces are allowed in the parameter lines. The parameter value must be decimal or hexadecimal (prefix 0x).
Note that the parameters are case-sensitive and that the order of the parameters cannot be changed.
Example of a parameter line:
General.EncoderType=SIM
Further information on the objects mentioned can be found in the
VLT
®
ISD 410 Design Guide.
.
Parameter
Description
Default Value
General.
General.BitRate
CAN baud rate for both CAN lines.
Possible values: 1000, 500, 250, 125, 50 kBaud
500
General.DefaultCanId
This value is used as the CAN-ID when the BCD switch is set to 0.
100
General.BaseCanId
When the BCD switch is not set to 0, then the CAN-ID = Bas BCD-value.
100
General.SecondCANLi-
neEnable
0 = CAN line II is disabled (default)
1 = CAN line II is enabled
0
General.EncoderType
Defines the default encoder; if left empty, simulation is default.
Possible values: SIM, SSI, QEP, SSI_CRC, BiSS
SIM
General.HeartbeatTime
Defines the interval for the transmission of the heartbeat in ms.
0 = disabled
Value range: 0-65535 ms.
0
General.MaxAngleDifference Maximum angle difference threshold allowed between 2 subsequent encoder samples
with scaling of 65536 for 360° or 1°
--> 1° x 65536/360° = 182.
This parameter affects emergency code 0xFF0B.
A value larger than 32768 disables monitoring.
184
General.WrongDirection-
Threshold
Wrong direction threshold with scaling of 65536 for 360° or 1° --> 1° x 65536/360° =
182.
This parameter influences emergency code 0xFF06.
A value larger than 32768 disables monitoring.
10
General.WrongDirec-
tionCheck
Enables wrong direction check.
1 = enabled (default)
This parameter influences emergency code 0xFF06.
1
RxPD01.
RxPD01.Cobld
COB-ID for RxPDO1
0x200+ $NODEID
TxPD01.
TxPD01.Cobld
DS406 position
0xC
$NODEID
TxPD01.EventTimer
Transmission interval in ms.
Value range: 0-65535 ms. 0 = disabled
0
TxPD02.
TxPD02.Cobld
COB-ID for position valid message
0x4
$NODEID
TxPD02.EventTimer
Transmission interval in ms.
Value range: 0-65535 ms. 0 = disabled
0
TxPD03.
TxPD03.Cobld
Position message ID
0x40000040
TxPD03.EventTimer
Transmission interval in ms.
Value range: 0-65535 ms. Default = 5 ms
5
Simulation.
Appendix
VLT
®
ISD Encoder Box Operating Instructions
36