ICM/ICAD Motorized Valve 

 

 

Installation, Programming, and Troubleshooting

 Danfoss (USCO / MKS), 11 - 006

 

DKRCI.EI.HT0.A1. / 50H1639   

       9

ICAD Parameters

Description

Display 

name

Min.

Max.

Factory 

setting

Unit

Comments

ICM OD (Opening 

Degree)

-

0

100

-

%

ICM valve Opening Degree is displayed during normal operation.

Running display value (see 

¡01

¡05

).

Main Switch

¡01

1

1

-

Internal main switch

1: Normal operation

: Manual operation. Valve Opening Degree will be flashing. With the down arrow 

and the up arrow push buttons the OD can be entered manually. 

Mode

¡02

1

1

-

Operation mode

1: Modulating – ICM positioning according to Analog Input (see 

¡03

)

: ON/OFF - operating the ICM valve like an ON/OFF solenoid valve controlled via  

Digital Input. See also 

¡09

.

Analog Input signal

¡03

1

4

-

Type of Analog Input signal from external controller

1: 0 - 0 mA

: 4 - 0 mA

3: 0 - 10 V

4:  - 10 V

Speed at ON/OFF and 

Modulating Mode

¡04

1

100

100

%

Speed can be decreased. Max. speed is 100 %

Not active when 

¡01

 = 

If 

¡02

 =  the display will indicate speed in display. 

Low

Med

 and 

High

 also 

means ON/OFF operation.

If 

¡04

 < = 33, 

Low

 is displayed

33 < If 

¡04

 < = 66, 

Med

 is displayed

If 

¡04

 > = 67 

High

 is displayed

Automatic calibration

¡05

0

1

0

-

Not active before 

¡26

 has been operated.

Always auto reset to 0.

CA

” will flash in the display during calibration, if Enter push button has been 

activated for two seconds. 

Analog Output signal

¡06

0

-

Type of A0 signal for ICM valve position

0: No signal

1: 0 - 0 mA

: 4 - 0 mA

Fail safe

¡07

1

4

1

-

Define condition at power cut when fail safe is installed.

1: Close valve

: Open valve

3: Maintain valve position

4: Go to OD given by 

¡12

Digital Input function

¡09

1

1

Define function when DI is ON (short circuited DI terminals) when 

¡02 

1: Open ICM valve (DI = OFF = > Close ICM valve)

: Close ICM valve (DI = OFF = > Open ICM valve)

Password

¡10

0

199

0

-

Enter number to access password protected parameters: 

¡26

Password =

 11

Old Alarms

¡11

A1

A99

-

-

Old alarms will be listed with the latest shown first. Alarm list can be reset by 

means of activating down arrow and up arrow at the same time for  seconds.

OD at powercut

¡12

0

100

50

-

Only active if 

¡07 

= 4

If fail safe supply is connected and powercut occurs ICM will go to entered OD.

ICM configuration

¡26

0

6

0

NB:

 Password protected. Password = 

11

At first start up 

A1

 will flash in display. Enter valve type

0: No valve selected. Alarm 

A1

 will become active.

1: ICM0 with ICAD 600

: ICM5 with ICAD 600

3: ICM3 with ICAD 600

4: ICM40 with ICAD 900

5: ICM50 with ICAD 900

6: ICM65 with ICAD 900

Programming the ICAD

When the ICAD motor is first powered, the ICAD display will flash an A1 alarm.  This means 
that the ICM valve size that is being used with the ICAD motor needs to be selected in 
parameter 

¡26

.  Parameter 

¡26

 is password protected and will not appear in the parameter list 

until the user enters the password in parameter 

¡10

.  The password is “11,”  and will allow the 

user to access parameter 

¡26

 where the appropriate valve size is selected.  When the ICM 

valve size is selected, the ICAD will calibrate itself to the ICM valve and will then be ready for 
control by a 4-0mA signal.  For most applications, this is the only programming that will 
need to be done if the ICAD is going to be controlled by a 4-0mA input.

Summary of Contents for ICM

Page 1: ...REFRIGERATION AIR CONDITIONING ICM ICAD Motorized Valve Installation Programming and Trouble shooting Quick Start Guide...

Page 2: ...and Troubleshooting DKRCI EI HT0 A1 22 520H1639 Danfoss USCO MKS 11 2006 Contents Page Installation 3 Wiring the ICAD 5 ICAD Overview 8 ICAD Programming 9 Troubleshooting The Manual Tool 10 Service pa...

Page 3: ...d must be separately removed from the valve body with a 12 mm hex key prior to welding see diagrams below Removing ICM 25 to 65 bonnets 1 Remove the 4 bolts 2 Rotate the bonnet as shown 3 Pry the bonn...

Page 4: ...4 ICM 65 110 81 7 Install the ICAD motor actuator on the ICM valve a The ICM valve must not be in its fully opened position while the ICAD motor is calibrated with the valve at a later step Therefore...

Page 5: ...on White common alarm digital NPN transistor output when combined with yellow wire Brown indicates ICM is fully open digital NPN transistor output when combined with yellow wire Green indicates ICM is...

Page 6: ...White Optional UPS battery back up Wiring diagram showing ICAD wired with a PLC or other type of third party electronics Note The ICAD supplies the power for the 4 20 mA feedback signal Wiring diagra...

Page 7: ...Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays Note The same 24 Vd c power supply that powers the ICAD can be used with the ICAD digital outputs to power au...

Page 8: ...valve position output signal to modulate another ICAD or to a PC or PLC for monitoring see parameter 06 p 6 4 Because the ICAD is employs a digital stepper motor its speed can be adjusted to any perc...

Page 9: ...safe is installed 1 Close valve 2 Open valve 3 Maintain valve position 4 Go to OD given by 12 Digital Input function 09 1 2 1 Define function when DI is ON short circuited DI terminals when 02 2 1 Ope...

Page 10: ...before using the manual tool and restore power afterward to ensure recalibration and trouble free operation The user will be able to troubleshoot and determine many of the conditions and set points wi...

Page 11: ...not appear to be opening or closing properly The ICAD was not mounted properly on the valve stem Solution Check to make sure that the ICAD was mounted evenly on the ICM valve The ICAD is not receiving...

Page 12: ...inuous power supply It is used to change the valve position usually to close the valve in the event of a power failure Therefore the system is not to be run in the UPS mode Add a solenoid valve in fro...