background image

ICM/ICAD Motorized Valve 

 

 

Installation, Programming, and Troubleshooting

DKRCI.EI.HT0.A1. / 50H1639 

 

 Danfoss (USCO / MKS), 11- 006

Care should be taken to protect the ICM function module while it is removed from the 
valve body.

3.  Weld the valve body in line making sure the arrow on the valve body is pointing in    
  the direction of flow.
4.  Remove all debris from the valve body before re-installing the bonnet.
5.  Install the bonnet/function module into the valve body.

  a.  For ICM 0, make sure that the removable orifice seat is installed in the valve body 

with the small O-ring between the orifice seat and body.  Make sure the bonnet gasket 
is installed and in good condition.

  b.  For ICM 5 through ICM 65, check that the two O-rings on the bonnet and gasket 

located between the bonnet and valve body are installed and in good condition.  A 
light coating of refrigerant oil on the bonnet O-rings will facilitate installation of the 
bonnet.

6.  Install the four bolts and torque to the following specifications:  

Valve body

Nm

ft lbs

ICM 0

50

37

ICM 5

80

59

ICM 3

80

59

ICM 40

90

66

ICM 50

100

74

ICM  65

110

81

7.  Install the ICAD motor actuator on the ICM valve:
 

a.  The ICM valve must not be in its fully opened position while the ICAD motor is 

calibrated with the valve at a later step.  Therefore, if the opening degree of the ICM 
valve was changed from the factory setting, it should be set to an opening degree 
between 0% and 75% using the manual magnet tool.  To easily ensure correct 
positioning, turn the manual tool counter-clockwise until it is clear that it cannot be 
turned further. 

  b.  Make sure that the ICM adapter/valve stem and inner ICAD motor magnets are 

completely dry and free from any debris.

  c.  For applications below freezing, the ICM adapter O-ring (position c in the diagram 

on page 3) must be removed, and Molycote G 4500 grease (supplied with ICAD 
motor) needs to be applied in the O-ring groove on the adapter and on the O-ring 
before it is re-installed on the ICM adapter.  The Molycote grease ensures a good seal 
between the ICAD motor and the ICM adapter to prevent moisture from entering the 
ICAD magnets.

  d.  Place the ICAD motor on the valve stem.
  e.  Push the ICAD motor completely down to the identification ring on the valve stem 

and use a .5 mm hex key to tighten the set screws evenly so the ICAD motor is 
centered on the ICM adapter (torque: 3 Nm/ .5 lb-ft).

Summary of Contents for ICM

Page 1: ...REFRIGERATION AIR CONDITIONING ICM ICAD Motorized Valve Installation Programming and Trouble shooting Quick Start Guide...

Page 2: ...and Troubleshooting DKRCI EI HT0 A1 22 520H1639 Danfoss USCO MKS 11 2006 Contents Page Installation 3 Wiring the ICAD 5 ICAD Overview 8 ICAD Programming 9 Troubleshooting The Manual Tool 10 Service pa...

Page 3: ...d must be separately removed from the valve body with a 12 mm hex key prior to welding see diagrams below Removing ICM 25 to 65 bonnets 1 Remove the 4 bolts 2 Rotate the bonnet as shown 3 Pry the bonn...

Page 4: ...4 ICM 65 110 81 7 Install the ICAD motor actuator on the ICM valve a The ICM valve must not be in its fully opened position while the ICAD motor is calibrated with the valve at a later step Therefore...

Page 5: ...on White common alarm digital NPN transistor output when combined with yellow wire Brown indicates ICM is fully open digital NPN transistor output when combined with yellow wire Green indicates ICM is...

Page 6: ...White Optional UPS battery back up Wiring diagram showing ICAD wired with a PLC or other type of third party electronics Note The ICAD supplies the power for the 4 20 mA feedback signal Wiring diagra...

Page 7: ...Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays Note The same 24 Vd c power supply that powers the ICAD can be used with the ICAD digital outputs to power au...

Page 8: ...valve position output signal to modulate another ICAD or to a PC or PLC for monitoring see parameter 06 p 6 4 Because the ICAD is employs a digital stepper motor its speed can be adjusted to any perc...

Page 9: ...safe is installed 1 Close valve 2 Open valve 3 Maintain valve position 4 Go to OD given by 12 Digital Input function 09 1 2 1 Define function when DI is ON short circuited DI terminals when 02 2 1 Ope...

Page 10: ...before using the manual tool and restore power afterward to ensure recalibration and trouble free operation The user will be able to troubleshoot and determine many of the conditions and set points wi...

Page 11: ...not appear to be opening or closing properly The ICAD was not mounted properly on the valve stem Solution Check to make sure that the ICAD was mounted evenly on the ICM valve The ICAD is not receiving...

Page 12: ...inuous power supply It is used to change the valve position usually to close the valve in the event of a power failure Therefore the system is not to be run in the UPS mode Add a solenoid valve in fro...

Reviews: