ICM/ICAD Motorized Valve 

 

 

Installation, Programming, and Troubleshooting

DKRCI.EI.HT0.A1. / 50H1639 

 

 Danfoss (USCO / MKS), 11- 006

ICAD Overview

Before programming it is important to understand the functionality of the ICAD actuator:

1.  The ICAD is a digital stepper motor.  As such, it will count steps up and down from the  

position it believes it is in.  Every time, the ICAD is powered on, it will drive itself to the  
closed position in order to re-establish its base point of reference.  It will then move back  
to the position corresponding to the signal it is receiving from the control wiring.

.  The ICAD can be put into manual mode to move it (using the up and arrows) to a location  

different from the location that the signal is telling it to be in 

(see parameter  ¡01, p. 6)

.  

When in the manual mode, the display screen will be flashing and will continue to flash 
flashing the % opening of the valve until the  ICAD is taken out of the manual mode.

3.  The ICAD can be operated in analog mode (for modulating operation) or in digital mode 

for solenoid operation.  The ICAD can receive a variety of control signals 

(see parameter 

¡03, p. 6) 

and can send a valve position output signal to modulate another ICAD or to a PC 

or PLC for monitoring. 

(see parameter ¡06, p. 6)

4.  Because the ICAD is employs a digital stepper motor, its speed can be adjusted to any 

percentage of full speed through the parameter menu. 

(see parameter ¡04, p. 6)

5.  The ICAD can be connected to a 4 VDC UPS (Uninterruptible Power Supply) and can be 

programmed for actions when the normal power has been cut and the ICAD is operating  
off of the UPS power. 

(see parameter ¡07 and ¡12 , p. 6)

1.  In order to access the menu,
  PRESS and HOLD the middle button () until the menu screen appears.

.  Once you are in the menu, use the up (3) and down (1) arrow keys to move through the  
  list of parameters.
3.  To display the current setting of a parameter press the middle button.

  a. To change the value of a parameter setting, use the up or down arrow to establish  

the new setting while in that particular parameter’s display mode.

  b. Once the new setting for a parameter has been selected, push the center button  to 

save the charge and return to the menu.

4.  Repeat this procedure for all parameters.  
5.  Exit from the parameter list by pressing and holding the middle button for  seconds.  
  The ICAD will automatically exit if no buttons are pushed for 0 seconds. 

Operating the ICAD Menu

1.  Down arrow push button

.  Enter

3.  Up arrow push button

4.  Display

Summary of Contents for ICM

Page 1: ...REFRIGERATION AIR CONDITIONING ICM ICAD Motorized Valve Installation Programming and Trouble shooting Quick Start Guide...

Page 2: ...and Troubleshooting DKRCI EI HT0 A1 22 520H1639 Danfoss USCO MKS 11 2006 Contents Page Installation 3 Wiring the ICAD 5 ICAD Overview 8 ICAD Programming 9 Troubleshooting The Manual Tool 10 Service pa...

Page 3: ...d must be separately removed from the valve body with a 12 mm hex key prior to welding see diagrams below Removing ICM 25 to 65 bonnets 1 Remove the 4 bolts 2 Rotate the bonnet as shown 3 Pry the bonn...

Page 4: ...4 ICM 65 110 81 7 Install the ICAD motor actuator on the ICM valve a The ICM valve must not be in its fully opened position while the ICAD motor is calibrated with the valve at a later step Therefore...

Page 5: ...on White common alarm digital NPN transistor output when combined with yellow wire Brown indicates ICM is fully open digital NPN transistor output when combined with yellow wire Green indicates ICM is...

Page 6: ...White Optional UPS battery back up Wiring diagram showing ICAD wired with a PLC or other type of third party electronics Note The ICAD supplies the power for the 4 20 mA feedback signal Wiring diagra...

Page 7: ...Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays Note The same 24 Vd c power supply that powers the ICAD can be used with the ICAD digital outputs to power au...

Page 8: ...valve position output signal to modulate another ICAD or to a PC or PLC for monitoring see parameter 06 p 6 4 Because the ICAD is employs a digital stepper motor its speed can be adjusted to any perc...

Page 9: ...safe is installed 1 Close valve 2 Open valve 3 Maintain valve position 4 Go to OD given by 12 Digital Input function 09 1 2 1 Define function when DI is ON short circuited DI terminals when 02 2 1 Ope...

Page 10: ...before using the manual tool and restore power afterward to ensure recalibration and trouble free operation The user will be able to troubleshoot and determine many of the conditions and set points wi...

Page 11: ...not appear to be opening or closing properly The ICAD was not mounted properly on the valve stem Solution Check to make sure that the ICAD was mounted evenly on the ICM valve The ICAD is not receiving...

Page 12: ...inuous power supply It is used to change the valve position usually to close the valve in the event of a power failure Therefore the system is not to be run in the UPS mode Add a solenoid valve in fro...