Operating Guide | iC7-Marine PROFINET
4.5.2
Active Front End Application Connectivity Settings
Table 18: General Connectivity Settings for Active Front End
Menu index
Parameter
Parameter number
Value
Description
2.9.8.1
Fieldbus Fault Response
1304
• Info (default)
• Warning
• Fault
• Fault, open MCB
See
for descrip-
tions of the events.
Select the behavior
when a fieldbus fault,
for example loss of I/O
connection occurs.
2.9.8.2
No Fieldbus Connection
Response
1305
• Info (default)
• Warning
• Fault
• Fault, open MCB
See
for descrip-
tions of the events.
Select the behavior in
case no active fieldbus
connection has been
established.
2.9.8.3
Process Data Timeout
Response
1306
• Info (default)
• Warning
• Fault
• Fault, open MCB
See
for descrip-
tions of the events.
Select the response in
case there is no fieldbus
connection.
2.9.8.4
Process Data Timeout
Time
1340
0.05–18000 s (Default
value: 1.00 s)
Set the timeout time. If
process data is not re-
ceived within the time
set, a process data time-
out is triggered.
2.9.8.5
Fieldbus Watchdog
Response
5244
• Info (default)
• Warning
• Fault
• Fault, open MCB
See
for descrip-
tions of the events.
Select the response
in case the fieldbus
watchdog bit (bit 11)
has not changed its
value within the specific
watchdog delay time.
Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A |
33