Operating Guide | iC7-Marine PROFINET
Menu index
Parameter
name
Parameter
number
Value
Additional information
10.3.2.2.1
Name of
Station
7080
Accepted characters:
• Lower case letters (a–z)
• Numbers (0–9)
• Special characters: dash (–), full stop (.)
The value can be up to 127 characters or
digits in total. The maximum length for
each component separated by a full stop
or dash is 63 characters or digits. Spaces
are not allowed.
Each PROFINET device has
a unique Name of Station.
4.3
GSDML File (Device Description File)
To configure a PROFINET controller, the configuration tool needs a GSDML file for each type of device in the network. The GSDML file is a
PROFINET xml file containing the necessary communication setup data for a device. Each product in the iC7 series has a unique GSDML
file.
Download the GSDML files for the iC7 series from
https://www.danfoss.com/en/service-and-support/downloads/dds/fieldbus-con-
. Check that the GSDML file version is compatible with the firmware version.
4.4
Reference and Main Actual Handling
4.4.1
Propulsion & Machinery Application
For the Propulsion & Machinery application the Main Reference [REF] and the Main Actual Value [MAV] are tied to the motor speed. These
variables are interfaced as signed 16-bit integer values and are both scaled linearly based on the signal and scale parameter pairs given
in
.
Table 15: Reference Scaling Parameters
Menu
index
Parameter
Parameter
number
Unit
Range
Data type
2.2.2.1.20
Fieldbus Speed Signal Max
6312
-
-32768–32767
Signed 16
2.2.2.1.21
Fieldbus Speed Signal Min
6313
-
-32768–32767
Signed 16
2.2.2.1.22
Fieldbus Speed Scale Max
6310
[Hz]
-1000–1000
Float 32
2.2.2.1.23
Fieldbus Speed Scale Min
6311
[Hz]
-1000–1000
Float 32
Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A |
29