Figure 9: Communication Port X0, X1, and X2 Locations in the Modular Control Unit
1
Ethernet port (X0)
2
Ethernet port (X1)
3
Ethernet port (X2)
3.5
EMC-compliant Installation
3.5.1
Overview
To obtain an EMC-compliant installation, follow the instructions provided in the product-specific design guide and the installation guide
included in the shipment.
3.5.2
Grounding
l
Ensure that all stations connected to the fieldbus network are connected to the same ground potential. When distances between
the stations in a fieldbus network are long, connect the individual station to the same ground potential. Install equalizing cables
between the system components.
l
Establish a grounding connection with low HF impedance, for example, by mounting the unit on a conductive backplate.
l
Keep the ground wire connections as short as possible.