7

Option A

Setting minimum heating temperature set point

This feature allows the building owner to determine the minimum heating temperature available to the user.

Option b

Setting maximum cooling temperature set point

This feature allows the building owner to determine the maximum cooling temperature available to the user.

Option C

Optimum start control, heating (OSC)

(not available if “Non-Prog” is selected on DIP switches 1 & 2)
This feature allows the installer to enable the optimum start control for the heating event. If enabled it allows the heating
to be turned on earlier than the programmed time in order to ensure that recovery of room temperature is achieved by the
programmed time. The setting is dependent upon the capacity of the system and the building heat gain/loss characteris-
tics and can be determined from the following table. If Option 4 (occupancy and smart-fan programming) has been
enabled, the optimum start control will operate at each occupied event change that requires an increase in temperature.
If Option 4 has been left in the disabled mode the optimum start controller will only function prior to the first event (Event
1) of the day

Estimate of system

temperature rise capability

Optimum start

Maximum duration

in  30  minutes

control  settings

of early on period

N/A

0

Optimizer disabled

16°F

1

15 mins

8°F

2

30 mins

5-6°F

3

45 mins

4-5°F

4

60 mins

3-4°F

5

75 mins

2-3°F

6

90 mins

2°F

7

105 mins

1-2°F

8

120 mins

Option d

Optimum start control, cooling (OSC) 

(not available if “Non-Prog” is selected on DIP switches 1 & 2)

This feature allows the installer to enable the optimum start control for the cooling event. If enabled it allows the cooling
to be turned on earlier than the programmed time in order to ensure that recovery of room temperature is achieved by the
programmed time. The setting is dependent upon the capacity of the system and the building heat gain/loss characteris-
tics and can be determined from the following table. If Option 4 (occupancy and smart-fan programming) has been
enabled, the optimum start control will operate at each occupied event change that requires a decrease in temperature. If
Option 4 has been left in the disabled mode the optimum start controller will only function prior to the first event (Event 1)
of the day.

Estimate of system

temperature reduction

Optimum start

Maximum duration

capability in 30 minutes

control settings

of early on period

N/A

0

Optimizer disabled

16°F

1

15 mins

8°F

2

30 mins

5-6°F

3

45 mins

4-5°F

4

60 mins

3-4°F

5

75 mins

2-3°F

6

90 mins

2°F

7

105 mins

1-2°F

8

120 mins

Option E

Setting thermostat calibaration

This feature allows the installer to calibrate the temperature shown in the LCD display by ± 3°F.

Summary of Contents for HP8211-1RJ

Page 1: ...ing the event times setbacks and temperatures ________________ 4 Summary table of Advanced Programing Mode APM options ______________ 5 Detailed description of Advanced Programming Mode APM options __...

Page 2: ...on the white tabs as this could damage the thermostat How to Lock the Front Cover If locking is required fit locking piece before fitting the thermostat to wallplate Do not close the front cover unti...

Page 3: ...2 2 Sensor A B C TS2 2 Sensor 1 2 A B C TS2 2 Sensor 3 THERMOSTATS ALL 8000 15 13 A B C TS2 2 Sensor A B C TS2 2 Sensor 1 2 A B C TS2 2 Sensor 3 A B C TS2 2 Sensor 4 Wiring Instructions for the thermo...

Page 4: ...r heating Note If Option 4 of the advanced programming section has been enabled factory default is disabled the fan operation and occupancy relay can also be set at this time following Step 3 below St...

Page 5: ...Temp 86 F 85 F to 43 F Used in conjunction with Option A 9 Min Cooling Temp 61 F 62 F to 104 F Used in conjunction with Option b A Min Heating Temp 43 F 44 F to 86 F Used in conjunction with Option 8...

Page 6: ...de the fan will operate in and what overrides will be available to the user Option 6 Selecting extent of keyboard disable function active only when dip switch 5 is set to keyboard disable This feature...

Page 7: ...nutes control settings of early on period N A 0 Optimizer disabled 16 F 1 15 mins 8 F 2 30 mins 5 6 F 3 45 mins 4 5 F 4 60 mins 3 4 F 5 75 mins 2 3 F 6 90 mins 2 F 7 105 mins 1 2 F 8 120 mins Option d...

Page 8: ......

Reviews: