DETAILED DESCRIPTION OF ADVANCED PROGRAMMING MODE (APM) OPTIONS

To enter Advanced Programming Mode (APM) press and hold FAN and COPY buttons for 3 seconds.  Note: the thermostat must be in
nomal running mode (not programming mode).

When in APM mode use the 

and

buttons to scroll through the options available.  Use the Next button to move onto the subsequent

option.

Option 1

Setting temperature override duration timer

(not available if “Non-Prog” is selected on DIP switches 1 & 2)
This feature allows the building owner to determine the duration of any temporary temperature override selected by the
user.

Option 2

Setting fan run-on after cooling demand

This feature allows the installer to select a timed fan run-on following each cooling demand.

Option 3

Setting fan run-on after heating demand

This feature allows the installer to select a timed fan overrun following each heating demand.

Option 4

Enabling or disabling programmable occupancy programming

(not available if “Non-Prog” is selected on DIP switches 1 & 2)
This feature allows the operation of the fan to be programmed to Auto or On, and the occupancy relay contacts to be
opened or closed, during each event.  Setting these options is affected during the event programming process.  See step
3 para 3.1 through to 3.5 on page 4.

Option 5

Setting fan operation mode

(not available if “Non-Prog” is selected on DIP switches 1 & 2)

This feature allows the building owner to determine what mode the fan will operate in and what overrides will be available
to the user.

Option 6

Selecting extent of keyboard disable function. active only when dip switch 5 is set to “keyboard disable”

This feature allows installer to determine the extent of the disablement of keyboard functions if DIP switch 5 is set to
“Keyboard disable”. See table below:

Feature

 Part (nor)

Full

Access to programming mode

Access to advanced programming mode

Access to service mode

Access to Hold & Vacation mode

Access to Daylight Savings Time Change

Selection of AM/PM or 24 hour clock

Selection of Fahrenheit or Centrigrade scaling

Mode select (auto/heat/cool/off)

Mode select (EM heat, Heat-pump models)

Fan Mode (Auto/On/Smart-fan)

Temperature override (including duration)

View temperature information

Change display time to temperature

Note :

Settings of options 7 through b are dependent on each other.  Not all settings will be accepted and an ERR message
may be experienced. If this occurs press (

) or (

) to make the setting valid.  Alternatively press NEXT button to return to

option 7 and review the settings.

Option 7

Setting heating / cooling dead-band adjustment 

(not available if “Changeover Manual” is selected on DIP switch 6)

This feature allows the installer or the building owner to determine minimum dead-band between heating and cooling.

Option 8

Setting maximum heating temperature set point

This feature allows the building owner to determine the maximum heating temperature available to the user.

Option 9

Setting minimum cooling temperature set point

This feature allows the building owner to determine the minimum cooling temperature available to the user.

Summary of Contents for HP8211-1RJ

Page 1: ...ing the event times setbacks and temperatures ________________ 4 Summary table of Advanced Programing Mode APM options ______________ 5 Detailed description of Advanced Programming Mode APM options __...

Page 2: ...on the white tabs as this could damage the thermostat How to Lock the Front Cover If locking is required fit locking piece before fitting the thermostat to wallplate Do not close the front cover unti...

Page 3: ...2 2 Sensor A B C TS2 2 Sensor 1 2 A B C TS2 2 Sensor 3 THERMOSTATS ALL 8000 15 13 A B C TS2 2 Sensor A B C TS2 2 Sensor 1 2 A B C TS2 2 Sensor 3 A B C TS2 2 Sensor 4 Wiring Instructions for the thermo...

Page 4: ...r heating Note If Option 4 of the advanced programming section has been enabled factory default is disabled the fan operation and occupancy relay can also be set at this time following Step 3 below St...

Page 5: ...Temp 86 F 85 F to 43 F Used in conjunction with Option A 9 Min Cooling Temp 61 F 62 F to 104 F Used in conjunction with Option b A Min Heating Temp 43 F 44 F to 86 F Used in conjunction with Option 8...

Page 6: ...de the fan will operate in and what overrides will be available to the user Option 6 Selecting extent of keyboard disable function active only when dip switch 5 is set to keyboard disable This feature...

Page 7: ...nutes control settings of early on period N A 0 Optimizer disabled 16 F 1 15 mins 8 F 2 30 mins 5 6 F 3 45 mins 4 5 F 4 60 mins 3 4 F 5 75 mins 2 3 F 6 90 mins 2 F 7 105 mins 1 2 F 8 120 mins Option d...

Page 8: ......

Reviews: