background image

© Copyright Danfoss | Commercial Compressors | 2014.12

FRCC.PI.015.A4.02 - December 2014 - 

8510274P01A

 •   Verify that the power supply corresponds to the 

compressor motor characteristics (see nameplate).

 

• 

 

When installing a compressor model, use 

equipment specifically reserved for HFC 

refrigerants which was never used for CFC or 

HCFC refrigerants.

 •  

Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 •   The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

 •   The compressor must always be mounted with the 

rubber grommets supplied with the compressor.

4 – Assembly

 

•  

Slowly release the nitrogen holding charge 

through discharge and suction ports.

 •  Connect the compressor to the system as soon as 

possible to avoid oil contamination from ambient 

moisture.

 •   Avoid material entering into the system while cutting 

tubes. Never drill holes where burrs cannot be removed.

 •  Braze with great care using state-of-the-art technique 

and vent piping with nitrogen gas flow.

 •  Connect the required safety and control devices. 

When the schrader port, if any, is used for this, 

remove the internal valve.

 •  For parallel assemblies of the compressors in 

version C8, contact Danfoss.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.

 •  Do not use leak detection dye.

 •   Perform a leak detection test on the complete system.

 •  The low side test pressure must not exceed 31 bar 

/450 psi.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.

 •   Connect a vacuum pump to both the LP & HP sides.

 •  Pull down the system under a vacuum of 500 µm 

Hg (0.67 mbar) / 0.02 inch Hg absolute.

 •  Do not use a megohmmeter nor apply power to 

the compressor while it is under vacuum as this 

may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.

 •   All electrical components must be selected as per 

local standards and compressor requirements.

 

•  

Refer to page 1 for electrical connections 

details.For three phase applications, the 

terminals are labeled T1, T2, and T3. For single-

phase applications the terminals are labeled C 

(common), S (start), and R (run).

 •  Danfoss scroll compressors will only compress gas 

while rotating counter-clockwise (when viewed 

from the compressor top). Since single-phase 

motors will start and run in only one direction, 

reverse rotation is not a major consideration. 

Three-phase motors, however, will start and 

run in either direction, depending on the phase 

angles of the supplied power. Care must be taken 

during installation to ensure that the compressor 

operates in the correct direction.

 •  Use ø 4.8 mm / #10 - 32 screws and ¼” ring terminals 

for the power connection with ring connect screw 

terminal (C type). Fasten with 3 Nm torque.

 •  Use ø 6.3 mm tabs for quick connect spade 

terminals (P type).

 

•  

Use a self tapping screw to connect the 

compressor to earth.

8 – Filling the system

 •  Keep the compressor switched off.

 •  Keep the refrigerant charge below the indicated 

charge limits if possible. Above this limit; protect 

the compressor against liquid flood-back with a 

pump-down cycle or suction line accumulator.

 •   Never leave the filling cylinder connected to the circuit.

Compressor models

refrigerant 

charge limit 

HRM032-034-038-040-042-045-047

3.6 kg / 8 lb

HRP034-038-040-042-045-047

HHP015-019-021-026

HRH031-032-034-036-038-040

HRM048-051-054-058-060 / 

HLM068-072-075-078-081

5.4 kg / 12 lb

HRP048-051-054-058-060 / 

HLP068-072-075-081

HHP030-038-045

HRH044-049-051-054-056 / 

HLH061-068 - HLJ072-083

HCM094-109-120

7.2 kg / 16 lb

HCP094-109-120

HCJ090-091-105-106-120-121

9 – Verification before commissioning

 Use safety devices such as safety pressure switch 

and mechanical relief valve in compliance with both 

generally and locally applicable regulations and 

safety standards. Ensure that they are operational 

and properly set. 

 Check that the settings of high-pressure 

switches don’t exceed the maximum service 

pressure of any system component.

 •  A low-pressure switch is recommended to avoid 

low pressure operation. 

Minimum setting for R22

1.5bar (absolute)/22 psia

Minimum setting for R407C

Minimum setting for R410A 2.5bar (absolute)/36 psia

 

 •   Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 24 hours before initial start-up 

and start-up after prolonged shutdown. 

 •  Please respect a 90 Nm ± 20 Nm for tightening 

torque of all rotolock nut.

10 – Start-up

 •  Never start the compressor when no refrigerant is 

charged.

 •  Do not provide any power to the compresor 

unless suction and discharge service valves are 

open, if installed.

 •  Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 

conformity and voltage on terminals.

 •   Eventual reverse rotation can be detected by 

following phenomena; the excessive noise, no 

pressure differential between suction and discharge, 

and line warming rather than immediate cooling. 

A service technician should be present at initial 

start-up to verify that supply power is properly 

phased and that the compressor is rotating in the 

correct direction. H-series Scroll compressors are 

designed to operate for a maximum of 150 hours 

in reverse, but as a reverse rotation situation can go 

unnoticed for longer periods, phase monitors are 

recommended. For compressors HLM078, HLP081, 

HLJ083 and larger, phase monitors are required for all 

applications. Danfoss recommends phase protection 

for residential compressors.

 •   If the internal overload protector trips out, it must cool 

down to 60°C / 140°F to reset. Depending on ambient 

temperature, this may take up to several hours.

11 – Check with running compressor

 Check current draw and voltage. Measurement of 

amps and volts during running conditions must be 

taken at other points in the power supply, not in the 

compressor electrical box.

 •  Check suction superheat to reduce risk of slugging.

 •  Observe the oil level in the sight glass (if provided) 

for about 60 minutes to ensure proper oil return to 

the compressor.

 •  Respect the operating limits.

 •    Check all tubes for abnormal vibration. Movements 

in excess of 1.5 mm / 0.06 in require corrective 

measures such as tube brackets.

 •   When needed, additional refrigerant in liquid phase 

may be added in the low-pressure side as far as 

possible from the compressor. The compressor must 

be operating during this process.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  

Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 

future inspections.

12 – Maintenance

  Internal pressure and surface temperature 

are dangerous and may cause permanent injury. 

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature may 

exceed 100°C / 212°F and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor problems, 

following periodic maintenance is recommended:

 •   Verify that safety devices are operational and 

properly set.

 •   Ensure that the system is leak tight.

 •   Check the compressor current draw.

 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  

 

Check that all electrical connections are still 

adequately fastened.

 •   Keep the compressor clean and verify the absence 

of rust and oxidation on the compressor shell, 

tubes and electrical connections.

 •  Acid / moisture content in system and oil should 

be checked regularly.

13 - Warranty

Always transmit the model number and serial 

number with any claim filed regarding this product.

The product warranty may be void in following 

cases:

 •    Absence  of  nameplate.

 

•  

 

External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •   Compressor opened or returned unsealed.

 •  

 

Rust, water or leak detection dye inside the 

compressor.

 •   Use of a refrigerant or lubricant not approved by 

Danfoss.

 •   Any deviation from recommended instructions 

pertaining to installation, application or 

maintenance.

 •   Use in mobile applications.

 •   Use in explosive atmospheric environment.

 •   No model number or serial number transmitted 

with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 

and compressor oil should be recycled by 

a suitable company at its site.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products 

already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Reviews: